Parking Frame - AUMA SAEx 07.2 Operation Instructions Manual

Multi-turn
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

SAEx 07.2
SAEx 16.2 / SAREx 07.2
ACExC 01.2 Intrusive HART
Design
Observe prior to connec-
tion
5.4.2.

Parking frame

Application
SAREx 16.2 Control unit - electromechanical
Figure 19: Design principle with wall bracket
[1]
Wall bracket
[2]
Connecting cables
[3]
Electrical connection of wall bracket (XM)
[4]
Electrical connection of actuator (XA)
[5]
Electrical connection of controls (XK)
Permissible length of connecting cables: max. 100 m.
If the actuator is equipped with a position transmitter (RWG): Connecting cables
must be available as shielded version.
Versions with potentiometer in the actuator are not suitable.
We recommend: AUMA cable sets LSW8-KES or LSW9-KP.
If the AUMA cable set is not used: Use suitable flexible and screened connecting
cables.
When using connecting cables, e.g. of the heater or switch, requiring direct
wiring from the actuator to the XK customer connector (XA-XM-XK, refer to
wiring diagram), these connecting cables must be subject to an insulation test
in compliance with EN 50178. Connecting cables of position transmitters (RWG,
IWG, potentiometer) do not belong to this group. They may not be subject to
an insulation test.
Parking frame for safe storage of a disconnected plug.
For protection against touching the bare contacts and against environmental
influences.
Figure 20: Parking frame and Ex plug/socket connector with screw-type terminals
(KP/KPH)
Electrical connection
customer connector
27