Configuration of Function Blocks
3-1-3

ITEMs Common to All Function Blocks

ITEM type
ITEM
Name
No.
Contact
000
Stop block
input
operation
command
Parameter 001
Comment
002
Block
Model
Special
003
Execution
error
display
Parameter 004
Operation
cycle
Note
84
Description
To stop operation of this function block using a FINS com-
mand, set this ITEM to 1. When this ITEM is returned to 0, a
hot start (state active before the Board was stopped is con-
tinued before operation is started) is performed.
Note
System Common block (Block Model 000) ITEM000
cannot be used. (Must be set to 0.)
A comment up to 23 characters long can be described in
this ITEM.
Note
The default in CX-Process Tool is the name of the
function block (eight letters).
Set the Block Model of the function block to be registered
(allocated) to blocks having this number. The settings of
ITEM006 onwards is determined according to the Block
Model set here.
An error code is stored here if the data that is set to each
ITEM in this function block is inappropriate, an error has
occurred in execution of the function block, or the function
block data is in error.
Note
For details of error codes, see 7-1 Errors and Alarm
Troubleshooting.
Specify the operation cycle group of this function block.
Specify whether to execute the function block at the opera-
tion cycle (standard setting) specified in the System Com-
mon block (Block Model 000), or to execute the block at a
different specific operation cycle group (1 to 5).
Note
To change the operation cycle, first set System
Common block (Block Model 000) ITEM014 to 0
(stop). The operation cycle cannot be changed
while the Loop Controller is running.
(1) ITEM types and settable modes are the same as for individual ITEMs
shown in 3-1-4 ITEMs Unique to Individual Function Blocks. For details of
each ITEM type, see the explanation for the individual function block.
(2) This function is enabled only for Basic PID (Block Model 011), Advanced
PID (Block Model 012), and Segment Program 3 (Block Model 158) with
LCB01/03/05 Version 3.5 or higher. When an execution error occurs, the
error can be cleared by setting ITEM 003 to 0.
Section 3-1
R/W mode
R: Read, W: Write, R/W: R/W-enabled,
-: R/W-disabled
Note: r and r/w: Read and write for
confirmation of CX-Process Tool oper-
ation
According
According
According
to CX-
to ITEM
to Step
Process
Setting
Ladder
Tool
block
Program
---
---
R/W
R/W
---
---
R/W
---
---
r
---
R/W (See
(W) (See
note 2.)
note 2.)
R/W
---
---