Omron SYSMAC CS Series Operation Manual page 91

Loop control boards, process-control cpu units, loop controller, loop-control cpu units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Specifications
Item
MV (Manipulated
Number of points
Variable)
Output range
Output refresh cycle
Auto/manual switch-
ing
High/low MV limit
MV high rate-of-
change limit
Preset MV switching
MV hold
MV tracking
MV compensation
Out-of-range pro-
cessing at MV output
destination block
MV error input
Alarm
PV alarm
Deviation alarm
State Output
Description
1 set
−320.00 to +320.00%
According to the specified operation cycle of this block
(one of 0.1, 0.2. 0.5, 1, 2 seconds)
Possible (according to CX-Process Tool or contact
signal from Sequence Table block/Step Ladder Pro-
gram block/Contact Distributor block)
High limit: −320.00 to +320.00%, low limit: −320.00 to
+320.00%
0 to 115.00%/s
When the preset MV switch is set to ON, the MV
switches to the preset MV (fixed value) and control is
continued at this value.
The MV (Manipulated Variable) is held at the current
value when the MV hold switch is ON.
The MV is switched (tracks) to the input value from
other blocks.
Arithmetic operation (addition, subtraction, substitu-
tion) is performed on the MV signals from the PID
control section when the MV compensation input
switch is ON.
PID accumulator is stopped when the range is
exceeded on the function block to which MV is con-
nected.
MV error is transferred to SCADA software or other
external device when the MV error contact turns ON.
4 (high/high limit, high limit, low limit, low/low limit),
setting range: each −15.00 to +115.00%
Hysteresis: 0 to +115.00%
1 (ON outside deviation)
1 current Set Point output (−15.00 to +115.00%),
1 deviation output (−115.00 to +115.00%)
Section 1-3
Basic
Ad-
PID
vanced
PID
×
59