How to Use the Sequence Table Block
Actions Section
Outputs
Contact outputs are set using one of the following notations.
Notation
Output
form
OUT_H
Holding
Y: ON when the condition is met and remains ON even when the condition is no
(destination)
longer met. Must be turned OFF from another rule.
N: OFF when the condition is met and remains OFF even when the condition is
no longer met. Must be turned ON from another rule.
OUT_L
Non-
Y: Remains ON while condition is met and remain OFF while condition is not met.
(destination)
holding
N: Cannot be specified.
OUT_P
Pulse
Y: ON only once when condition is met and turns OFF the next operating cycle.
(destination)
The condition must be not met and then met again before the signal will turn ON
again.
N: Cannot be specified.
OUT_F
Flashing
Y: Changes between ON and OFF when the condition is met and continues flash-
(destination)
ing even when the condition is no longer met.
N: The flashing output is turned ON while the condition is met and remains. ON
even when the condition is no longer met.
Note: To turn OFF and output that is being held ON, Use OUT_H with an N spec-
ification. Even when this is done, however, the signal will not turn OFF until the
condition for OUT_F is no longer met (for both a Y and N specification).
Note Any of the following parameters can be set as the destination.
• Function block address.ITEM number
• CSV tag name.tag ITEM
• User link table tag name
• The following can also be specified in Element Display Mode
Element numbers previous specified in Element Display Mode plus the following:
In YN column for TIM or CNT: Y = Reset start, N = Timer start
In YN column for TIM_PS: Y = Pause timing, N = Resume timing
The CX-Process Tool's Output Tab Settings
270
Operation
Appendix B
Y/N in rule
Execution
condition
Y (ON) or
When condi-
N (OFF)
tion changes
from not met
to met
Only Y
While condi-
(always ON)
tion is met
Only Y
When condi-
(pulse out-
tion changes
put)
from not met
to met
Y (flashing)
While condi-
or N
tion is met
(remains ON
when flash-
ing stops)