How to Use the Sequence Table Block
Basic Structure of the Sequence Tables
Only the LCB05/05D supports sequence tables. With the standard table settings, up to 200 tables combining
main tables and reference tables can be used and each table can have up to 32 rules (with up to 32 conditions
and 32 actions).
It is also possible to specify expanded settings for up to 64 rules (and up to 64 conditions/actions) in each table.
If expanded settings are used, the maximum number of tables is reduced. If just the rules column or conditions/
actions column is expanded, the expanded table occupies two standard tables. If both just the rules column
and conditions/actions column are expanded, the expanded table occupies four standard tables.
Standard
LCB05/05D: 200 tables max.
Table number
Table number
Table number
Symbol
32 conditions
Condition
max.
signals
Action
32 actions
signals
max.
NEXT STEP
Only Conditions/Actions Columns Expanded
LCB05/05D: 100 tables max.
Table number
Table number
Symbol
Condition
64 conditions
signals
max.
Action
64 actions
signals
max.
NEXT STEP
Note To expand the number of conditions and actions in a table, use the CX-Process Tool and select Expand
- Vertical from the Operation Menu.
260
32 rules max. and 32 steps max.
Rule
1
2
Step
00
64 max.
THEN
To M
ELSE
Table number
32 rules max. and 32 steps max.
Rule
1
2
- - -
Step
00
- - -
THEN
To M
ELSE
N
32
32 max.
Appendix B