Configuration of Function Blocks

3-1

Configuration of Function Blocks

3-1-1

Configuration of Function Blocks

3-1-2

Preparing Function Block Data Sheets

Note
1,2,3...
82
All Loop Controller functions can be achieved by connecting the function
blocks in the software.
Function blocks comprise data items called ITEMs each starting from 000.
Function block
ITEMs 000 to 004 are common to all function blocks.
ITEM006 and onwards differ according to the Block Model.
CX-Process Tool is used to set data to each item in each function block, and
prepare function block data sheets. Function blocks are registered to function
block data sheets by being allocated to a block address (address for execu-
tion). These function block data sheets need only be transferred (downloaded)
to the Loop Controller to enable use of the Loop Controller. Function block
data sheets are prepared as function block files appended with the .ist exten-
sion.
When the Loop Controller is shipped from the factory, function block data
sheets are not stored on the Unit. Be sure to prepare function block data
sheets using CX-Process Tool and transfer (download) the sheets to the Loop
Controller.
Follow the procedure below to prepare and download function block data
sheets.
1. Allocate the function blocks to block addresses.
Select the function blocks to be used, and allocate them to block address-
es in the function block data sheets. Function blocks become executable
data once they have been allocated to block addresses. Allocatable block
addresses are determined as follows according to the type of function
block. Block addresses other than these cannot be allocated.
Function block type
Control blocks and oper-
ation blocks
External Controller
blocks
Sequence Control blocks Step Ladder Program block
Field Terminal blocks
ITEM
Data
000
001
002
003
004
Basic PID (Block Model 011)
and other Control blocks
Square Root (Block Model
131) and other Operation
blocks
External Controller block
(Block Model 301)
Sequence Table block (Block
Model 302)
Section 3-1
Allocatable block
address
LCB05/05D: 001 to 500
LCB03: 001 to 003
LCB01: 001 to 050
601 to 632
LCB01: 701 to 720
LCB03/05/05D: 701 to 900
901 to 980