Errors and Alarm Troubleshooting
LED Indicators
LED
on front of
Indicator
Loop
on front of
Controller
CPU Unit
RDY
EXEC
ERR/ALM
(See note.)
Not lit
Not lit
Lit
(A42403,
the Flash
Memory
Data Error
Flag or the
Duplex
Function
Block Data-
base (RAM)
Error Flag,
is ON.)
Flash-
Not lit
Flashing
ing
(A42410,
the RAM
Error Flag
is ON.)
226
Problem
Cause
Parameter
One of the following
backup
problems was detected
data (flash
during a cold start.
memory)
1) The data was cor-
error
rupted by noise or
other factor.
2) The power was inter-
rupted during a backup.
Note: If the function
block database
(RAM) is valid,
the data will be
backed up
again the next
time the power
is turned ON.
Parameter
One of the following
problems was detected
while restoring data
using the simple
backup function.
• The Memory Card is
not mounted.
• The Loop Controller
model is different
from that used to cre-
ate the project saved
in the Memory Card.
• The function block
data backed up in the
Memory Card is cor-
rupted.
• There is an empty
backup file on the
Memory Card cre-
ated for a simple
backup operation
performed for a Loop
Controller for which a
password has been
set.
• The unit version of
the LCB backed up in
the Memory Card is
higher than the unit
version of the LCB at
the recovery desig-
nation.
Note: Turn the CPU
Unit power from
OFF to ON
while pin 7 of
the DIP switch
on the front of
the CPU Unit is
ON.
Status
Error
code
(Stored
in error
log.)
Operation is
0331
stopped.
The
details
code con-
tains
either the
relevant
block
address
or FFFF if
all data
bases are
invalid.
Operation is
None
stopped.
Section 7-1
Corrective action
Execute the Download or
Clear all operation from CX-
Process Tool Version 3.0.
The Flash Memory Data Error
Flag (A42403) will go OFF if
the data in RAM becomes
valid.
Reinstall the Memory Card
used to back up the function
block data (using simple
backup), and cycle the CPU
Unit power while leaving pin 7
of the DIP switch on the front
of the CPU Unit turned ON.