Kinetix 5700 Regenerative Bus Supply

Ground Jumper Settings

The regenerative bus supply includes a ground jumper that is installed at the factory. Keep the
ground jumper installed when input power has a grounded-wye configuration. Remove the
ground jumper when using impedance-grounded power configurations. Refer to the
Kinetix 5700 Servo Drives User Manual, publication 2198-UM002, for configuration diagrams.
IMPORTANT
ATTENTION: Risk of equipment damage exists. The input-power ground configuration must be
accurately determined. When the ground jumper is installed with impedance-grounded power
distribution or when the ground jumper is not installed with grounded-wye power distribution,
damage to equipment can result.
ATTENTION: Risk of equipment damage exists. If you are using the 2198-RP
supply, always remove the ground jumper in 2198-D -ERS and 2198-S -ERS inverters.
ATTENTION: To avoid personal injury, the ground jumper access door must be kept closed when
power is applied. If power was present and then removed, wait at least 5 minutes for the DC-bus
voltage to dissipate, and verify that no DC-bus voltage exists before accessing the ground jumper.
The ground-jumper access door is located on the front of the regenerative bus supply. To access
the ground jumper, insert a small screw driver or probe into the door release slot and push the
door up behind the cover.
Remove the Ground Jumper
6
If you have grounded-wye power distribution in your facility, do not remove the ground
jumper from the regenerative bus supply. For all other power distribution configurations,
refer to the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002, to determine
the ground jumper setting.
Ground Jumper Access Door
(behind cover)
Door Release Slot
Ground Jumper
TIP
Hold the jumper with
needle-nosed pliers and
loosen captive screws.
Rockwell Automation Publication 2198-IN014A-EN-P - August 2018
Ground jumper installed
for grounded WYE power configuration
(jumper installed is default setting).
Remove jumper for impedance-grounded
power configurations.