DeDietrich GSHP 5 MR-E User Manual page 33

Geothermal heat pump
Hide thumbs Also See for GSHP 5 MR-E:
Table of Contents

Advertisement

Parameters
SUM/WIN
CALIBR.OUT
OFFSET ROOM A
OFFSET ROOM B
OFFSET ROOM C
PERMUT
CALIBR.ROOM A
CALIBR.ROOM B
CALIBR.ROOM C
ANTIFR.ROOM A
ANTIFR.ROOM B
ANTIFR.ROOM C
7636860 - v04 - 18012017
Description
Outside temperature above which the heating will be shut
down:
OFF : The heating is never shut down automatically.
Can be set from 15 to 30°C:
The heating pumps are shut down.
The heat pump only starts up for domestic hot water or
cooling needs, if the function is enabled.
The
symbol is displayed.
The symbol
is displayed if the cooling function is ena­
bled,
Outside sensor calibration
Is used to correct the outside temperature information.
Room temperature offset on circuit A.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Can be set from -5 to +5°C.
Room temperature offset on circuit B.
Is used to set a room temperature offset.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Can be set from -5 to +5°C.
Room temperature offset on circuit C.
Is used to set a room temperature offset.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Can be set from -5 to +5°C.
Used to establish the pilot heat pump:
AUTO : the pilot heat pump automatically switches every 7
days
Can be set from 1 to 10: number of the heat pump chosen
as the pilot heat pump
Calibration of the room temperature sensor on circuit A.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Calibration of the room temperature sensor on circuit B.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Calibration of the room temperature sensor on circuit C.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Room temperature at which frost protection on circuit A is ac­
tivated.
Can be set from 0.5 to 20°C.
Room temperature at which frost protection on circuit B is ac­
tivated.
Can be set from 0.5 to 20°C.
Room temperature at which frost protection on circuit C is
activated.
Can be set from 0.5 to 20°C.
Factory setting
Customer setting
22°C
Outside tempera­
ture
0
0
0
AUTO
Room tempera­
ture on circuit A
Room tempera­
ture on circuit B
Room tempera­
ture on circuit C
6°C
6°C
6°C
GSHP
6 Settings