Why don't the values displayed on the web page match
the values displayed in the Skymetry software?
• The web page displays a snapshot of the values at a particular
moment in time. It does not display real-time values, as is the
case when connected locally through the Skymetry software.
• Click the Status Update button on the web page to retrieve a
current snapshot.
Why can't I get pump control to work?
• The Output(s) are not set to Pump Control mode.
• The Pump Control parameters are programmed incorrectly.
• The level transducer is not wired to analog input #6.
• The level transducer is not reading the proper values.
• The float switches are not wired to Dry Contact inputs #6, #7,
and #8.
• The float switches are not Normally Open.
• The Lead, Lag, and Pumps-Off float switches are not wired to
the proper inputs.
Appendix B: Troubleshooting