Click the down arrow in the Input Trigger field to select the input
that will initiate the event. If you select a Dry Contact input, you
can have the event occur when the selected input goes from Open-
to-Closed or Closed-to-Open. If you select an Analog input you can
have the event occur if the input is equal-to, greater-than, or less-
than a specified value.
Enter a value for the comparison (range: -16,384 to 16,383).
Note: peer-to-peer events are triggered as soon as
the input meets the trigger conditions. There is no
recognition time applied in this case. Also, peer-to-
peer events will not be executed while you are on
line locally.
Next, enter the SkyID and Password of the WTU-14 unit whose out-
put you want to switch. Select the output number and action (either
ON or OFF). Click Apply or OK when finished. Remember, the tar-
get output must be set to manual mode, otherwise the command will
be ignored. If the password is wrong the command will be ignored
as well.

Local Output Control

You can perform control logic using the same inputs and outputs on
a single WTU-14 unit. If you want to switch an output on the same
Skymetry WTU-14 as the input, then simply enter the unit's own
SkyID (a password is not required in this case). The output must be
set to manual mode. Local output control does not use any airtime
and also executes instantly (as long as there are no preceding peer-to-
peer events that must communicate with a different WTU-14 device).
60
Figure 2: Peer-to-peer Edit screen