Skymetry WTU-14 Manual
• The output you are trying to switch is not set to manual mode.
• The input condition for the machine-to-machine command is not
being met.
My unit won't execute a Remote machine-to-machine com-
mand.
• Machine-to-machine commands will not execute while you are
connected locally.
• The output on the remote unit you are trying to switch is not set
to manual mode.
• The input condition for the machine-to-machine command is not
being met.
• The SkyID and Password for the remote unit is programmed
incorrectly.
My WTU-14 isn't displaying the correct value from my
4–20mA transducer.
• The analog input jumper isn't set to the 4–20mA position.
• The analog input "type" isn't set to 4–20mA in the software.
• The transducer is not wired correctly.
• The transducer is not calibrated for the desired measurement
range.
• The analog input table values aren't programmed to the calibrat-
ed range of the transducer.
• The transducer is not compatible with single-ended inputs there-
fore an isolation device is required.
My temperature sensor isn't displaying the correct value.
• The analog input jumper isn't set to the Temperature position.
• The analog input "type" isn't set to Temperature in the software
• The temperature sensor isn't a compatible 10K thermistor.
• The temperature sensor isn't wired correctly.