Mounting rules
AM/AMS units (DC powered)
...................................................................................................................................................................................................................................
Horizontal rack mounting
Please observe the following rules for horizontal rack mounting:
• The units should be distributed equally within the rack.
• The minimum distance between two units must be 100 mm [3.937"] (measured
from top of the lower unit to bottom of the upper unit).
• It is required to use a heat baffle if more than 5 units are installed.
• A maximum of 10 units can be mounted within one rack. In that case a heat baffle
must be placed in the middle of the rack as shown in the figure below.
Note that the1643 AMS does not support 300 mm racks for 10 unit horizontal
mounting.
Figure A-1 Horizontal mounting (AM/AMS, DC)
...................................................................................................................................................................................................................................
A-2
Rack
AM/AMS
min. 100 mm
AM/AMS
min. 100 mm
AM/AMS
min. 100 mm
AM/AMS
min. 100 mm
AM/AMS
Heat Baffle
AM/AMS
min. 100 mm
AM/AMS
min. 100 mm
AM/AMS
min. 100 mm
AM/AMS
min. 100 mm
AM/AMS
Alcatel-Lucent - Proprietary
See notice on first page
365-312-802R7.2
Issue 4, June 2007