Zone Trigger Mode; 4204 Mode And Two-4204 Mode; Module Supervision Features - Honeywell AlarmNet 7845GSM Installation And Setup Manual

Digital cellular communicator
Hide thumbs Also See for AlarmNet 7845GSM:
Table of Contents

Advertisement

7845GSM/7845GSMCN Installation and Setup Guide
• The control treats the module as a Long Range Radio (LRR) device, so program the control
accordingly, including setting the module's proper LRR device address
• Reports are sent in Contact ID format
• The module also supports two hardwire zone trigger inputs (zones 6 and 7)

Zone Trigger Mode

• This mode is for use with controls that do not support LRR-ECP communication nor 4204
Relay Modules
• The module provides six input zones
• Each zone can be configured for +V, -V, or EOLR triggering
• Each zone can be programmed for inverted operation, delayed reporting, and restoral
reporting
• Zone 1 input can distinguish between pulsed and steady signals and report fire or
burglary alarms respectively
• Zone 1 can also be programmed to report Lynx panic (if used with Lynx control)
• Reports are sent in ADEMCO High-Speed format

4204 Mode and Two-4204 Mode

• This mode is for use with Honeywell controls that do not support LRR-ECP
communication, but that do support 4204 Relay Modules
• The module connects to the control's keypad terminals
• The control treats the module as 4204 Relay Module(s), so program the control
accordingly, including setting the module's proper 4204 device address
• 4204 mode provides up to four zone inputs, plus two optional trigger zones, depending on
options programmed
• Two-4204 mode provides up to eight zone inputs, depending on options programmed
• Each 4204 zone can be programmed for delayed reporting and restoral reporting
• Reports are sent in ADEMCO High-Speed format

Module Supervision Features

The 7845GSM provides the following types of supervision and module fault detection:
• Network communication failure: In the event the AlarmNet network does not hear a
supervisory message from the module within a specified time ("Supervision" option, 24
hours, 30 days, or none), AlarmNet notifies the central station of a communication failure.
• Communication path failure: In the event the module detects a communication path
failure, the control panel can be notified of a trouble condition with the module after a
specified time has elapsed ("GSM Flt Time" option, 00-99 minutes).
• Fault output: Terminal 11 can serve as a fail-safe trigger for module fault conditions.
If used, the fault relay will trip when the following conditions occur: tamper*, power loss*,
low battery*, battery charger fault*, loss of network connectivity*, the device is not
registered and the device is remotely disabled by AlarmNet.
*Alarm reporting for the noted condition must be enabled for it to trigger the fault relay.
• Primary power loss and low battery conditions ("Pwr Loss Rpt," "Low Bat Rpt" options).
• Cover tamper condition ("Tamper Rpt" option).