Quick Start Guide
6
Verify configuration
Before operating the flowmeter in an installation, you should review the
configuration data to ensure that it reflects the current application. In most
cases, all of these variables are pre-configured at the factory. Configuration
may be required if your flowmeter is not configured or if the configuration
variables need revision. Rosemount recommends the following variables are
reviewed before startup.
HART
•
Tag
•
Transmitter Mode
•
Process Fluid
•
Reference K-Factor
•
Flange Type
•
Mating Pipe ID
•
PV Units
•
PV Damping
•
Process Temperature Damping
•
Fixed Process Temperature
•
Auto Adjust Filter
•
LCD Display Configuration (For units with a display only)
•
Density Ratio (For Standard or Normal flow units only)
•
Process Density and Density Units (For mass flow units only)
•
Variable Mapping
•
Range Values
•
Pulse Output Configuration (For units with a pulse output only)
Foundation fieldbus configuration
•
Tag
•
Transmitter Mode
•
Process Fluid
•
Reference K-Factor
•
Flange Type
•
Mating Pipe ID
•
PV Units (configured in the AI block)
•
Flow Damping
•
Process Temperature Damping
•
Fixed Process Temperature
•
Auto Adjust Filter
•
LCD Display Configuration (for units with a display only)
•
Density Ratio (for Standard or Normal flow units only)
22
™
Rosemount
8800D Series Vortex Flowmeter
October 2018