Figure 2-4: Improper installation
2.1.5 Upstream/downstream requirements
The flowmeter may be installed with a minimum of ten straight pipe
diameters (D) upstream and five straight pipe diameters (D) downstream by
following the K-factor corrections as described in the 8800 Installation Effects
Technical Data Sheet (00816-0100-3250). No K-factor correction is required if
35 straight pipe diameters upstream (35D) and 10 straight pipe diameters
downstream (10D) are present.
2.1.6 External pressure/temperature transmitters
When using pressure and temperature transmitters in conjunction with the
flowmeter for compensated mass flows, install the transmitters downstream
of the flowmeter as shown in
Quick Start Guide
Figure
2-5.