eLecTrIcAL INSTALLATION

6.6 Temperature detection T1, T2

Parameter In.17 displays in high byte the installed temperature input of the drive con-
verter. The KEB COMBIVERT F5 / F6 is delivered as standard with switchable PTC / KTY
evaluation. The desired function is adjusted with Pn.72 (dr33 at F6) and operates in
accordance with the following table:
In.17 Function of T1, T2
KTY84
5xh
PTC
(in accordance with
EN
60947-7-1)
6xh
PT100
Table 25:
Temperature detection T1, T2
The column is valid at factory setting. The function must be programmed accordingly with parameters
1)
Pn.12, Pn.13, Pn.62 and Pn.72 for F5 in operating mode GENERAL.
2)
Disconnection is depending on the adjusted temperature in Pn.62 (F6 => pn11/14).
Dependent on the application the temperature input can be used for the following func-
tions:
Function motor temperature display
Motor temperature display and monitoring
Motor temperature monitoring
Temperature control for liquid-cooled motors
General fault sensing
Table 26:
Function motor temperature display
1)
If the temperature input is used for other functions, the motor temperature control at liquid-cooled drive
converters can be done indirectly via the liquid cooling circuit of the drive converter.
ATTENTION
Pn.72
resistance
(dr33)
< 215 Ω
498 Ω
0
1 kΩ
1.722 kΩ
> 1811 Ω
< 750 Ω
0.75...1.65 kΩ
(reset resistance)
1
1.65...4 kΩ
(tripping resistance)
> 4 kΩ
The behaviour of the drive converter in case of error/warning is defined with
parameters Pn.12 (CP.28), Pn.13 (F6 =>pn12/13).
1)
Do not lay KTY or PTC cable of the motor (also shielded) together
with control cable !
KTY or PTC cable only permissible with double shielding within the
motor cable !
Display ru.46
(F6 => ru28)
Detection error 253
1°C
100 °C
200°C
Detection error 254
T1-T2 closed
T1-T2 closed
T1-T2 open
T1-T2 open
upon request
Mode (F5 => Pn.72; F6 => dr33)
KTY84
PTC
KTY84
PTC
error/Warn-
ing
1)
x
2)
X
2)
X
2)
x
x
x
73