PrOTecTION OF DrIVe cONVerTerS

8 Protection of drive converters
Use the following fuses in the mains cable:
(rated current maximum 100 kA SCCR)
Size
Table 28:
* Version without UL approval.
All indications are permitted maximum values and apply to each module.

8.1 Use of circuit breakers

Drive converter F5 / F6
28
29
30
32
33
34
35
36
37
38
Table 29:
Use of circuit breakers
400 V
Type
ce
gG
500
28
630
29
630
30
500
32
500
33
630
34
630
35
500
36
630
37
630
38
-
39
Protection of drive converters
Input voltage in V
480 / 3ph
480 / 3ph
480 / 3ph
480 / 3ph
480 / 3ph
480 / 3ph
480 / 3ph
480 / 3ph
480 / 3ph
480 / 3ph
480 V
600 V
ul.
USA*
rk5/J
J
400
350
500
400
600
450
400
350
450
350
500
400
400
450
500
350
600
350
600
400
-
450
UL 489 Mccb in A
400
600
600
2 x 400
2 x 600
2 x 600
2 x 600
3 x 500
3 x 600
3 x 600
690 V
ce
gG
400
500
500
400
400
500
500
400
400
500
500
Siemens cat. No.
3VL400/JG-frame
3VL400X/LG-frame
3VL400X/LG-frame
2x 3VL400/JG-frame
2x 3VL400X/LG-frame
2x 3VL400X/LG-frame
2x 3VL400X/LG-frame
3x 3VL400X/LG-frame
3x 3VL400X/LG-frame