Wiring; Alarm Contact Wiring; Control Output Wiring - Honeywell PW6K1OUT Installation Manual

Table of Contents

Advertisement

Note:
and use as the common; use the orange pair as your data pair, observing
polarity. Connect the external drain shield to the appropriate earth ground on
one end.
5. When daisy-chaining RS-485 ports together, connect the TR+ wires from the
By factory default J1 is set open. If this board is the last board on the RS-485 bus,
install jumper J1 across both pins (closed). Closing J1 provides the bus termination
required.

Wiring

This section presents information on alarm contact wiring and control output wiring.

Alarm Contact Wiring

Inputs TMP and PFL are typically used for monitoring cabinet tamper and power
failure respectively. These two inputs are not supervised and are not accessible when
the board is rack-mounted. These inputs are used when this board is mounted remotely
and cannot take advantage of the tamper and power fail detect inputs on the Controller
board. If these inputs are not used, install a short piece of wire at the input to indicate
safe condition.

Control Output Wiring

Sixteen form-C relay contacts are provided as general-purpose outputs. They are
configurable as standard (energize to activate) or fail-safe (de-energize to activate) by
the host software.
The energized or ON time of each relay can be configured using pulse control for
single or repeating pulses via the host software. The energized or ON time of a single
pulse can be extended up to 24 hours. For repeating pulses, the on/off time can be
defined in 0.1 second increments and be repeated up to 255 times.
All 16 relays are rated for dry contact signal or load switching. While they are sized to
handle typical loads, load switching can cause abnormal contact wear and premature
PW-6000 Output Module Installation Guide, Document 800-01953, Revision B
For RS-485 Communication Connections, twist the blue pair together
upstream and downstream boards to the TR+ terminal. Likewise, connect the
TR- wires from the upstream and downstream boards to the TR- terminal.
Installing the PW-6000 Output Module
Wiring
7