Navigating To The Third Setup Screen; Service Timeout; Node Address; Password - Emerson RLDS Installation And Operation Manual

Refrigerant leak detection system
Table of Contents

Advertisement

7.14. Navigating to the Third
Setup Screen
From the second System Setup screen, select the
MORE option to go to the System Setup screen 3. 
Select the BACK option to return to the System Setup
screen 2.
Figure 7-5 - Setup Screen 3

7.15. Service Timeout

NOTE: The RS485 BAUD rate text will be re-
placed by "Service Timeout" when in Service
Mode.
Displayed in Service Mode, Service Timeout sets the
length of time the Service Mode is in effect and stops
the monitor for up to 300 minutes (5 hrs) to 
allow for servicing the unit.
1. Press the ENTER key to adjust the setting.
2. Use the left/right cursor keys to move across
the entry field and the up/down cursor keys to
modify the individual numbers.
3. Press ENTER to accept the new entry or ESC
to revert to the previous setting.
30 • RLDS I&O Manual

7.16. Node Address

Each RLDS on the network must have a distinct node
address. The node address may be set from 1 to 64.
1. Press the ENTER key to adjust the setting.
2. Use the left/right cursor keys to move across
the entry field and the up/down cursor keys to
modify the individual numbers.
3. Press ENTER to accept the new entry or ESC
to revert to the previous setting.

7.17. Password

This field is used to define a system password. The
default setting is 000, which provides no password
protection.
1. Press the ENTER key to adjust the password.
2. Use the left/right cursor keys to move across
the entry field and the up/down cursor keys to
modify the individual alphanumeric characters.
3. Press ENTER to accept the new password or
ESC to revert to the previous setting.
7.18. Accessing Additional
Features
Several additional features can be viewed on the Sys-
tem Setup screen 3 when the RLDS is placed in Ser-
vice Mode (refer to Section 8.11., Service Mode).
While in service mode, the user can identify the 
model number, set digipot values and sensor 
temperature, and acquire the temperature coefficient.
026-1309 Rev 8