Rlds - Connecting External Alarms; Overview; Connection - Emerson RLDS Installation And Operation Manual

Refrigerant leak detection system
Table of Contents

Advertisement

5
RLDS -
Connecting
External Alarms

5.1. Overview

Each RLDS includes four (4) Form C, SPDT 
relays. The contacts are rated .5A at 250 VAC and
1.0A at 30 VAC. These relays are used for the 
connection of external alarm devices. The relays are
factory-assigned to the following conditions:
Relay #1
Relay #2
Relay #3
Relay #4

5.2. Connection

Use the AC conduit or any of the remaining 
service knockouts to gain cable access to the interior
of the monitor. Locate the relay connector 
(Figure 3-9) and remove it from the circuit board.
1. Secure the leads to the connector orienting
them as shown in Figure 5-1. Wire the leads to
either the N.C. or N.O. terminals of each relay,
depending on whether you want the relay to be
CLOSED or OPEN when de-energized.
2. When you are through securing the 
connections, carefully plug the connector back
onto the circuit board.
Figure 5-1 - RLDS Relay Connector
22 • RLDS I&O Manual
Leak
Spill
Evacuate
Fault
NOTE: Each relay may be connected as nor-
mally open (NO), or normally closed (NC).
The relay contacts are rated .5 A at 250 VAC.
Latching / Non-Latching - refer to Section 7.7.,
Alarm Acknowledge (Ack) - Mode to select Alarm
Ack Mode.
Alarm power source - power for the alarm devices
connected to the relay contacts may be supplied from
the Auxiliary AC Power Out Connector (Figure 3-8).
Red*
Yellow*
Leak \ Spill \ Evacuate \ Fault
RELAY
Strobe or
Horn
LINE POWER
Figure 5-2 - RLDS Relay 1 and 2 Wiring
3. Jumper the Neutral of the input power 
connector to the Common on the relay block.
4. Connect one end of strobe or horn to the NO of
whichever level of alarm is appropriate for 
application.
5. The other end of strobe or horn is connected to
the Line of the input power connector (5 A
maximum).
*The colors correspond to
the LEDs on the front of the
case
Normal Configuration:
Strobes
are usually connected
to the Leak relay (#1)
Horns are usually connected
to the Spill relay (#2)
External Power:
AC < 250V
DC < 15W
Note: the device does not power
accessories; power must come from
an external source
026-1309 Rev 8

Advertisement

Table of Contents
loading

Table of Contents