11 Main Screens
11.1. Home Screen (F1
Screen)
Press F1 at any point to save changes and display the
Home screen:
RLDS GW-810-3760
VER: 1.10B04
FAIL:
I/O NET
(PRESS DOWN ARROW)
The HHT is used to display the following on the
Home screen:
• RLDS GW-810-3760: Model information
• 1.10B04: Version number
• FAIL: I/O NET: Displays the operation mode
on the third line of the HHT screen. This
indicates which type of area controller the
RLDS Gateway is attached to. The dip switch 8
is set to ON or OFF.
ON = REFLECS, OFF = E2, Einstein. If a
failure condition exists with the RLDS
Gateway, this line shows one of the following
failure messages:
FAIL: I/O NET indicates that no communication
with the I/O Net exists, and that communication
between the controllers is down.
FAIL: FLASH/CLK indicates the hardware is bad
and the Gateway should be replaced.
FAIL: USER CFG indicates that no RLDS units
have been found on the network, and have not been
configured by the user.
FAIL: RLDS CTRL indicates that one or more
RLDS controllers are down.
• PRESS DOWN ARROW indicates what to do
next.
NOTE: Pressing the down arrow scrolls you to
the next screen.
52 • RLDS I&O Manual
11.2. RLDS Enable Screen
The second screen will show whether a particular unit
is enabled, disabled, or unknown. When the RLDS
Gateway first powers up it will show
UNKOWN for all units. It will then start scanning for
each unit. If it finds a unit, it marks it as ENABLED.
If an RLDS is not present on the network, the user can
mark that RLDS as DISABLED to prevent the Gate-
way from scanning for that unit. When the unit is dis-
abled, the Gateway stops trying to access the RLDS
controller and does not respond to the
association request on the I/O Network.
RLDS LIST:
RLDS1: ENABLED
RLDS2: DISABLED
RLDS3: DISABLED
Press the down arrow to go to the next screen:
11.3. SELECT RLDS Screen (F2
Screen)
Press F2 at any point to save changes and display the
SELECT RLDS screen:
SELECT RLDS: 1
LDS1: ONLINE
RLDS2: DISABLED
RLDS3: DISABLED
NOTE: SELECT RLDS: 1 defaults to 1.
The F2 screen allows you to select the desired RLDS.
The F2 screen shows the general ONLINE or OF-
FLINE status for the enabled RLDS controllers. ON-
LINE means the Gateway is successfully
communicating with an enabled RLDS controller. If it
is unknown whether an RLDS is present on the
network, the screen will display UNKNOWN.
026-1309 Rev 8