12 RLDS Setup on
REFLECS, E2, and
Einstein
Controller
Interfaces
Dip switch 8 on the Gateway should be set to the OFF
position for E2, Einstein and the ON position for 
REFLECS controllers.

12.1. REFLECS Setup for RLDS

Set dip switch 8 to ON and follow the steps for setting
up RLDS units through the REFLECS controller in-
terface:
1. Log on.
2. Press 7 for Configuration to reach the 
CONFIGURATION screen.
Input Definitions should be set here to show how the
sensor control is linked to the zone. The number of 
devices and RLDS units are connected to the 
Gateway and enabled is the number of address slots
the Gateway will use.
3. Press 1 for Input Definitions to reach the 
INPUT DEFINITIONS screen.
4. Pressing the down arrow several times will get
you to the input list of SENS01-48. Bd (board)
is the address of the Gateway, Pt (point) is the
zone and allows you to define where the sensor
input comes from.
The board number for the RLDS setup is the 
address of the Gateway. If there are three or less
RLDS controllers connected to a Gateway, the 
Gateway address = the RLDS address. However, if
there are more than three RLDS controllers, the 
second Gateway address will be the one entered for
the board number, but the RLDS controllers are set 1
to 3 on the second Gateway.
5. Press 0 (zero) to go back to the 
CONFIGURATION screen.
6. Press 7 for I/O Brd Setup to reach the I/O
BOARD MENU screen.
60 • RLDS I&O Manual
7. Press 2 to Set Device #'s.
The Gateway will react as three 16AI boards. The
number of RLDS controllers plus the real number of
16AIs = the total number of 16AIs to enter in the next
step:
8. At the I/O BOARD DEVICE NUMBERS
screen, press the down arrow key to reach
Number 16AI Boards and enter the number of
how many 16AI boards and RLDS controllers
there are. Press Enter.
9. Arrow down to the I/O BOARD MENU and
press 0 (zero) twice to go back to the MAIN
MENU screen.
10.Press 4 for Sensor Control.
11.Press 2 for Setup--up to 48 sensor control 
programs are allowed. Select one of the 48
units and press Enter to reach the SENSOR
SETUP screen.
12.Press the right arrow to move to the Name field
to change the name, and press the down or right
arrow to move to the (sensor) Type field. Use
the "." and "—" keys to scroll through the 
options and select IRLDS.
13.Use the arrow keys to move off the active fields
and press 0 (zero) twice to go back to the main
screen.
12.2. E2 Version 3.01 and below
Setup for RLDS (without
Gateway)
Set dip switch 8 to OFF and follow the steps for s
etting up RLDS units through the E2 controller 
interface
1. Log in to the E2 with Level 4 access.

2. Press
- Connected I/O Boards
026-1309 Rev 8