E2, Einstein, And Reflecs Controllers (The Rlds Gateway Board); Powering The Gateway Board; Gateway Board Networking - Emerson RLDS Installation And Operation Manual

Refrigerant leak detection system
Table of Contents

Advertisement

4.2. E2, Einstein, and
REFLECS Controllers
(The RLDS Gateway
Board)
12
Figure 4-6 - RLDS Gateway Board Layout (P/N 810-3760)
NOTE: Before installing the Gateway board,
verify that jumper JP7 (if present on the board)
is set to the "NORMAL" position (not the
"TEST" position). Operating the Gateway with
the jumper in TEST position may cause board damage.
The RLDS may be connected to an Emerson 
Electronics and Solutions controller using a Gateway
Board. The Gateway Board is a special interface 
device that allows an E2, Einstein, or REFLECS site
controller to communicate with up to three RLDS
units as if each of them were a standard 16AI Analog
Input board, and allows for programming with the
Hand-Held Terminal (HHT).
The Gateway Board communicates with the RLDS
units via the MODBUS network, which is 
connected to the Gateway's "Receiver Bus" network
terminal. The Gateway communicates with site 
controllers (E2, Einstein, or REFLECS) via the 
RS485 I/O Network (COM A & COM D for 
REFLECS).
16 • RLDS I&O Manual
12
JP7
In addition to being an interface with the site 
controller, the Gateway Board also allows you use a
Hand-held Terminal (HHT) device to program the
RLDS and view status.

4.2.1. Powering the Gateway Board

Input Voltage
Power
Table 4-1 - Gateway Power Requirements
The Gateway board requires 24VAC power from a
Class 2 center-tapped transformer.
Emerson Electronics and Solutions supplies 
several sizes of center-tapped transformers for 
powering multiple 16AIs, 8ROs, and other RS485 
peripheral boards of the E2, Einstein, and REFLECS
systems.
Refer to your controller's user manual for 
information on how to use the center-tapped 
transformers listed in Table 4-2 to power multiple
RS485 I/O devices.
Figure 4-7 shows how to connect the 56VA and
80VA transformers to the Gateway power connector.
Three-Board
P/N
640-0056
Power Rating
Table 4-2 - Power Ratings for Emerson Transformers
Figure 4-7 - Pinout for the 56VA (640-0056) and 80VA (640-
0080) Transformers
24VAC, Class 2, 50/60Hz
5VA
Six-Board
640-0080
56 VA
80 VA
026-1309 Rev 8