Time/Date Screen; Calibrate Gas Screen 1; Calibrate Gas Screen 2; Calibrate Gas Screen 3 - Emerson RLDS Installation And Operation Manual

Refrigerant leak detection system
Table of Contents

Advertisement

NOTE: When setting up multiple zones in one
area (such as a motor room), stagger these
zones as they enter the RLDS. For example, if
there are two motor rooms served by one
RLDS, each motor room has three sensing zones. Make
the first motor room zones 1, 3, and 5, and make the
second motor room zones 2, 4, and 6. This will allow the
leak detection system to return to that area being sensed
more regularly.
If the zone exists in a location where air flow will
affect the dispersion of refrigerant, reduce the alarm
limits to a lower level than usual. This will allow for
dispersion of the refrigerant in the air.

11.4.8. Time/Date Screen

From the CONFIG OPTION screen, set the time and
date. Press the right arrow key and select 2. Press the
down arrow key twice to open the TIME/DATE
screen:
1-DATE:
xx-xx-xx
1-TIME: xx:xx:xx
NOTE: For TIME, enter military time only.
A change in the Time/Date on any one of the RLDS
controllers changes ALL of the RLDS controllers on
the network.
Press the right arrow key to edit the fields. The right
and down arrow keys scroll downward through the
list, while the left or up arrow keys will backspace the
arrow so you may go back to change a field.
Press the up arrow key to scroll back up to the 
CONFIG OPTION screen to calibrate gases. Your
changes are saved and the data is written when you
scroll back up to the CONFIG OPTION screen.

11.4.9. Calibrate Gas Screen 1

CAUTION: The Calibrate Gas screens are
rarely used. Before modifying values in the
Calibration screens, contact your Emerson
Electronics and Solutions representative for
Correction Values.
56 • RLDS I&O Manual
The Calibrate Data message is used to calibrate the
gases used. It is read only if the user enters the 
configuration screen for HHT screens.
From the CONFIG OPTION screen, press the right
arrow key and then press the 3 key for 
CALIB GASES. Press the down arrow key twice and
wait for the WAITING ON READ FROM RLDS
message to clear to display the Calibration Gas
screens.
x - R11: xxx.x 
x - R12: xxx.x 
x - R22: xxx.x 
x - R23: xxx.x
NOTE: User enter a floating point number
for x.
Press the down arrow key so the Calibrate Gas Screen
1 will cycle through all gases and view the available
gases in the gas library. Press the down arrow key to
cycle Calibrate Gas screens 2 and 3 to complete the
calibration process:

11.4.10. Calibrate Gas Screen 2

1 - CURVE 1: xxx
1 - CURVE 2: xxx
1 - CURVE 3: xxx
<blank>
NOTE: User enter a curve number for New
Gas Type 1 for x.
Use the "." and "—" keys to scroll through the sup-
ported gas/refrigerants.
Press the down arrow key:

11.4.11. Calibrate Gas Screen 3

User can select names for each new gas/refrigerants
by pressing the right arrow key to activate the field
and using the "." and "—" keys to toggle the letters.
026-1309 Rev 8