Testing In Charge Mode And Ac Bypass Mode - Xantrex Freedom SW 230V Installation Manual

Freedom sw 230v sine wave inverter/chargers
Table of Contents

Advertisement

Installing the Inverter/Charger
If the light does not come on, make sure the voltage at the
DC terminals on the Freedom SW 230V is correct, as
described in "Step 7: Performing Checks Prior to Initial
Start-Up" on page 40.
2. After initialization, observe that none of the lights on the
front panel should remain illuminated.
3. Press the INVERTER ENABLE button. Verify that the
INVERTER ENABLED LED status light illuminates.
4. Connect the Freedom SW 230V to the test load by closing
the AC breaker that controls the circuit that the test load is
connected to.
If the light bulb illuminates, the Invert mode is working.
5. Press the Inverter Enable button to disable the inverter.
The INVERTER ENABLED LED status light is off.
42

Testing in Charge Mode and AC Bypass Mode

1. Close the AC supply breaker to supply AC power to the
unit.
To verify that the Freedom SW 230V starts charging:
2. After a few seconds, verify that the AC/Charge light on
the front panel is turned on (indicating that the batteries
are being charged).
To verify that Freedom SW 230V correctly switches to
Bypass mode:
3. Disable the AC source and turn off the inverter by
pressing the Inverter Enable button.
4. Connect the test load to the AC output connection of the
unit.
5. Enable the AC source and the test load should turn on
after ten seconds.