2.
After the initial flash, verify that the lights on the front panel
illuminate as follows:
The Charger Enable button light is illuminated
The Network light is illuminated
All other lights are not illuminated
3.
Press the Inverter Enable button. Verify that:
The Inverter Enable button light illuminates
The Invert On light illuminates
4.
Connect the Freedom SW 3000 to the test load by closing the AC
breaker that controls the circuit that the test load is connected to.
If the light bulb illuminates, the Invert mode is working.
5.
Press the Inverter Enable button to disable the inverter. The Invert On
light and Inverter Enable button light are off.
975-0546-01-01

Testing in Charge Mode and AC Bypass Mode

1.
Close the AC supply breaker to supply AC power to the unit.
To verify that the Freedom SW 3000 starts charging:
2.
After a few seconds, verify that the Bulk light illuminates. Over a
period of time, the Absorption or Float light illuminates as charging
progresses.
In three-stage charging, the Bulk, Absorption and Float lights
illuminate in sequence.
In two-stage charging, the Bulk and Absorption lights illuminate
in sequence.
To verify that Freedom SW 3000 correctly switches to Bypass mode:
3.
Press the Charger Enable button to disable the charger. Verify that:
The Charger On light and Charger Enable button light turn off.
The AC load is still powered.

Installation Complete

Your installation is now complete. The inverter/charger is ready for use.
The preceding tests use a light load (a light bulb) as a test case. If you
encounter problems when using a load over 1000 W (for example, a
hairdryer or microwave), see the troubleshooting information in the
Freedom SW 3000 Sine Wave Inverter/Charger Owner's Guide.