Step 5: Connecting The Battery Temperature Sensor (Bts); Mounting Options - Xantrex Freedom SW 230V Installation Manual

Freedom sw 230v sine wave inverter/chargers
Table of Contents

Advertisement

Step 5: Connecting the Battery Temperature Sensor (BTS)

Installing a battery temperature sensor (BTS) extends the life
of a battery by preventing overcharging in warm temperatures
and undercharging in cold temperatures. With a BTS
monitoring the battery temperature, the voltage delivered to
the battery is adjusted according to the battery's actual
temperature.
The BTS has a self-adhesive backing and attaches to the side
of the battery. A 7.6 m cable is supplied with the BTS.

Mounting Options

You can mount the BTS in one of two ways:
Mounting the sensor to the negative battery post allows
the internal battery temperature to be sensed and provides
the most accurate results.
Attaching the sensor to the side of the battery using the
self-adhesive backing also provides good results in most
situations.
975-0697-01-01
Connector
Sensor cable
Sensor
Figure 10 BTS with Cable
EQUIPMENT DAMAGE
Use only the Freedom SW 230V-compatible Battery Temperature Sensor
(BTS). To order a spare BTS, call customer service and order part number
809-0946.
Failure to follow these instructions can damage the unit and/or damage
other equipment.