NOTE: The DC grounding conductor may be one size smaller than the minimum size conductor required for the DC current carrying conductors providing the overcurrent protection device in the DC
positive conductor is rated no greater than 135% of the ampacity of the DC grounding conductor and the conductor is no smaller than 2mm
Figure 4 Wiring and Breakers Block Diagram for Freedom SW 230V 2524 / 3524
975-0697-01-01
INVERTER AC SUB PANEL (TYPICAL)
15 A
20 A
Neutral
GND
MAIN ELECTRICAL PANEL
30 A
NEUTRAL = BLUE
GND = GREEN WITH YELLOW STRIPE
Neutral
GND
IMPORTANT: Read Owner's and Installation
Guides prior to installation. Always refer to local and
national electrical codes for proper wire and breaker