6. Strip approximately 50 mm off the jacket from the AC
cable and separate the wires.
7. Using a 6 mm blade slot screwdriver, loosen the terminal
screws on the terminals. Do not remove the screws.
8. Connect the line and neutral wires to the input terminals
(labeled AC Input on the terminal block, Figure 6 on page
26) as follows:
Connect Line to INPUT L, Neutral to INPUT N.
9. Tighten the terminal screws. Leave some slack wire
inside the wiring box.
10. Connect the ground wires to a free position on the ground
bus, Figure 6 on page 26. If solid ground wire is being
used, the wire can be connected directly under the screw
heads. If stranded ground wire is being used, ring
terminals must also be used.
11. Secure the strain-relief clamp on the AC input cable
jacket.
975-0697-01-01

Connecting the AC Output Wires

EQUIPMENT DAMAGE
Do not connect the output of the inverter to any AC source.
Failure to follow these instructions can damage the unit and/or damage
other equipment.
To make the AC output wiring connections:
1. Remove one of the AC knockouts from the front or side
of the unit. Do not leave the knockout inside the wiring
compartment.
IMPORTANT:
The applicable installation code may not allow you to run
the AC input and AC output wiring through the same AC knockout.
2. Install a strain-relief clamp in the AC knockout and run
the AC wiring through the strain-relief clamp.
3. Strip approximately 50 mm off the jacket from the AC
cable and separate the wires.
4. Using a 6 mm blade slot screwdriver, loosen the terminal
screws on the AC output terminals. Do not remove the
screws.