Installing the Inverter/Charger
Step 7: Performing Checks Prior to Initial Start-Up
Before testing your installation, ensure these conditions are
met:
❐ Chassis and AC grounds are properly installed
❐ AC input connections and AC output connections are
wired correctly on the terminal block and not reversed
❐ Positive (+) battery cable is connected to the positive (+)
battery terminal through the DC fuse and disconnect
switch or DC circuit breaker
❐ Negative (–) battery cable is connected to the negative (–)
battery terminal
❐ Battery voltage is within the proper range of 20–32 volts
DC
❐ DC disconnect switch or breaker is turned off
❐ AC input and output breakers are turned off
❐ All connections are tight
40