NOTE: All transfer specifications are at nominal conditions: ambient temperature of 25 °C, 230 VAC, 50 Hz input, unless
otherwise specified.
Transfer and General
Specifications
Transfer time—utility to invert
Minimum AC input voltage for transfer
Maximum AC input voltage for transfer
Minimum AC input frequency for transfer
Maximum AC input frequency for transfer
Cooling
Regulatory Approvals
Safety
EMC
975-0697-01-01
All Models
< 20 ms
170 VAC
270 VAC
45 Hz
68 Hz
Fan-cooled, temperature controlled.
All Models
CE mark (Europe)
EN62040-1
RCM mark (Australia)
AS 62040.1.1
AS/NZS 60335.2.29
CE (Europe) and RCM (Australia)
EN 62040-2
Specifications