Programming the Panel
Alarm Verify
(0516)
(Default = off) This setting determines whether the panel
reports to the central monitoring station after a single
sensor/zone trip (off) or waits for a second trip before
reporting (on).
This setting affects sensors/zones learned into groups 10
through 20. If Alarm Verify is set to on, group 18 responds
the same as group 17. See "Appendix A, Table A.3: Sensor
Group Characteristics."
Ìi
For UL Listed systems, Alarm Verify must be
turned off.
To turn Alarm Verify off or on:
With the display showing ALARM VERIFY OFF/ON
(current setting), press
flashes the entered setting. Press
shows the new setting.
System Tamper
(0517)
(Default = off) This setting determines whether or not the
armed system goes into alarm if several incorrect access
codes (40 consecutive keystrokes) are entered. This setting
also determines whether or not the panel reports to the
central station if a bus device stops communicating with the
panel.
To change the System Tamper setting:
With the display showing SYSTEM TAMPER OFF/ON
(current setting), press
flashes the entered setting. Press
shows the new setting.
Siren Options Menu
The SIREN OPTIONS menu lets you set up siren operation
and supervision.
The following describes how to program the siren option
settings that appear under GLOBAL.
28
(Reporting—Partition 1)
1 (off) or 2 (on). The display
ƒ and the display
(Reporting—Partition 1)
1 (off) or 2 (on). The display
ƒ and the display
Immediate Beeps
(0600)
(Default = off) This setting determines whether the panel
activates trouble beeps immediately (on) once a wireless
device supervisory condition is detected, or only if the
condition exists at panel supervisory time (off). (Refer to
TIMERS—GLOBAL—SUPERVISORY TIME.)
Ìi
For UL Listed systems, this feature must be on.
To turn Immediate Beeps off or on:
With the display showing IMMEDIATE BEEPS OFF/
ON (current setting), press
display flashes the entered setting. Press
display shows the new setting.
Disable Trouble Beeps
(0601)
(Default = off) This setting determines whether or not the
panel activates trouble beeps when a wireless device
supervisory condition is detected.
Ìi
For UL Listed systems, this feature must be off.
To turn Disable Trouble Beeps off or on:
With the display showing DISABLE TR BEEPS OFF/
ON (current setting), press
display flashes the entered setting. Press
display shows the new setting.
UL 98 Options
(0602)
(Default = off) This setting determines whether or not the
panel complies with UL 98 requirements (4-hour trouble
beep restart, 4-hour backup battery test, 2-hour supervisory
time period for sensor group 26—Fire).
Ìi
For UL Listed systems, this feature must be on.
To turn UL 98 Options off or on:
With the display showing UL 98 OPTIONS OFF/ON
1 (off) or 2 (on). The display
(current setting), press
flashes the entered setting. Press
shows the new setting.
(Siren Options—Global)
1 (off) or 2 (on). The
ƒ and the
(Siren Options—Global)
1 (off) or 2 (on). The
ƒ and the
(Siren Options—Global)
ƒ and the display