Buffer Memory List; Buffer Memory/Configuration - Mitsubishi Electric QJ71PB93D User Manual

Melsec q series profibus-dp slave module
Table of Contents

Advertisement

3
SPECIFICATIONS

3.4 Buffer Memory List

3.4.1 Buffer memory/configuration

Buffer memory address
Hexadecimal decimal
0
0
H
Output receive area
BF
191
H
C0
192
H
System area (Use prohibited)
FF
255
H
100
256
H
Input send area
1BF
447
H
1C0
448
H
System area (Use prohibited)
1FF
511
H
200
512
Operation baud rate
H
201
513
Operation station number
H
202
514
Station number set on flash ROM
H
203
515
Station number change request area
H
204
516
Station number rewritable count to flash ROM
H
205
517
H
System area (Use prohibited)
7F7
2039
H
7F8
2040
Module error information
H
7F9
2041
H
Extension trouble information area
805
2053
H
806
2054
H
System area (Use prohibited)
8CD
2253
H
8CE
2254
Current operation mode
H
8CF
2255
Operation mode change request area
H
8D0
2256
Operation mode change result
H
8D1
2257
Current communication watchdog timer value
H
8D2
2258
Self-diagnostic status type code display area
H
8D3
2259
Swapping function setting status
H
8D4
2260
H
System area (Use prohibited)
8DF
2271
H
8E0
2272
H
Output receive area used status
8EB
2283
H
8EC
2284
H
System area (Use prohibited)
8EF
2287
H
8F0
2288
H
Input send area used status
8FB
2299
H
8FC
2300
H
System area (Use prohibited)
AFF
2815
H
3 - 14
The configuration of the buffer memory used to receive and send data with the
QJ71PB93D and the CPU module is described below.
Area name
POINT
Do not write any data in the "system area (Use prohibited)" of the buffer memory.
If data is written to the "system area (Use prohibited)", there is a risk that the
programmable controller system may malfunction.
Description
Stores the output data received from the master station.
(Max. usable range 122 words)
Used to set the input data to be sent to the master station.
(Max. usable range 122 words)
Stores the baud rate in current operation.
Stores the station number in current operation.
Stores the station number saved on the flash ROM.
Used to set a new station number to be set in response to the station
number change request signal (Y13).
Stores the remaining number of times when the station number can be
saved onto the flash ROM during continuous operation.
Stores the error code detected by the QJ71PB93D.
Used to set the extension trouble notification data to the master
station.
Stores the operation mode in current operation.
Used to set a new operation mode to be set in response to the
operation mode change request signal (Y11).
Stores the result of changing the operation mode in response to the
operation mode change request signal (Y11).
Stores the communication watchdog timer value in current operation.
Stores the diagnostic status type code at the time of self-diagnostics.
Stores the setting status of the swapping function in current operation.
Stores the current used status of the output receive area.
Stores the current used status of the input send area.
MELSEC-Q
Read/Write
Read
Read/Write
Read
Read
Read
Read/Write
Read
Read
Read/Write
Read
Read/Write
Read
Read
Read
Read
Read
Read
3 - 14

Advertisement