Installation Guide E1100
Safety notes for the installation according to U L
Markings:
Use 60/75 °C or 75 °C copper wire only.
Maximum ambient temperature 40°C.
Suitable for use on a circuit capable of delivering not more than 5kA RMS symmetrical amperes, 85VDC
Maximum.
Motor over temperature sensing must be provided externally in the end-use
Terminal tightening torque:
X1, X2: 0.5 Nm (4.5 lbin), Screw thread: M2.5
X4:
0.25 Nm (2.2 lbin), Screw thread: M2
Wiring diagram conductor cross-section:
X1:
2.5mm
X4:
0.5 - 1.5mm
Ground terminal:
Threaded Grounding Bolt: M5 (located on the lower side of the housing). Marked with
Fuse Replacement:
CAUTION: For continued protection against risk of fire, replace only with same type and rating of fuse!
The fuses are directly soldered onto the PWB. Replacement is only possible by qualified personnel with appropriate
equipment.
Internal Fuse F2:
Internal Fuse F300:
Branch circuit protection of the motor power supply must be provided externally with a UL listed JDDZ RK-5 class
fuse (Fusetron FRN-R-20, 20A, 125VDC, UL File E4273).
Motor Phase Wiring:
For UL applications the motor phases have to be wired on X2 and not on X3!
Regeneration Resistor:
For UL applications pins RR+ and RR- of terminal X1 must not be connected!
In case of over voltage see chapter "Regeneration of Power / Regeneration Resistor" Option A.
NTI AG, LinMot
2
(AWG 14)
2
(AWG 21 – 14)
3A slow blow (Schurter OMT125, 3404.0118.xx, UL File Number: E41599)
16A slow blow (Schurter SMD-SPT, 0001.2716.xx, UL File Number: E41599)