RMTXX1 Series - IntelliPoint RF™ Instruction Manual
CE Installation Supplement (Continued)
3. Remote Installations
4. Housings
5. Sensor Type/Mounting
D. Comments:
Sensor port must be connected to the transmitter port by one of the
following means:
•
401-16 Probe Filter
•
Coaxial cable run in conduit.
•
Triaxial cable.
All installations require the sensor and transmitter to be located in
a closed shielded/metal housing (i.e. typically explosion-proof or
weatherproof housings meet this requirement)
In all non-metallic applications the sensor must have a full
concentric shield (i.e. needs to be considered when ordering).
The sensor/sensor condulet must be grounded locally either to a
metal support structure or an equivalent earth ground.
Any deviation from these installation requirements should
be reviewed with factory, prior to implementation
These instructions are essential to insure conformity with specified
EC directives.