Section 2: Installation
2.1

Unpacking

2.2

Mounting and Installation Guidelines

Cable fittings
supplied are weather-
resistant. They are
NOT certified as
explosionproof (XP) or
flameproof (d) unless
they are specifically
marked.
Carefully remove the contents of the shipping carton and
check each item against the packing list before destroying
any packing material. If there is any shortage or damage
report it to the factory immediately.
The IntelliPoint RF instrument can be mounted vertically,
horizontally, or at an angle. The mounting location should
be as free as possible from vibration, corrosive atmospheres,
and the possibility of mechanical damage. Ambient
temperatures at the electronics should be between -30 to
70ºC (-22 to 158ºF).
The IntelliPoint RF utilizes a dual compartment housing and
a completely encapsulated input/output module, to reduce
the possibility of damage occuring from water migrating into
the housing through the conduit.
To further reduce the possibility of damage caused by water
in the conduit, install a drip loop and breather drain to purge
any accumulating moisture. Refer to Figure 2-1.
When properly installed, the GREEN LED will illuminate
when power is applied. The two (2) RED LEDs should not be
flashing.
If either of the RED LEDs are flashing, refer to Section 4,
Troubleshooting.
Recommended Conduit Connection
5

Installation

Figure 2-1