2.6

Circuit Board

POWER
GREEN
ALARM
RED
OUTPUT CURRENT
8mA - ALARM
16mA - NORMAL
22mA - FAULT
8mA - NORMAL
16mA - ALARM
5mA - FAULT
HLFS
FAILSAFE
LLFS
HLFS
FAILSAFE
LLFS
2.6.1 Time Delay
The circuit board is located on the sensing element/circuit side of
the housing (marked on label). Remove the housing lid to access
the setpoint adjustment status LEDs, time delay adjustment,
and configuration jumpers. See Figure 2-4.
SETPOINT
CLOCKWISE WILL RAISE
OPERATING LEVEL
COUNTERCLOCKWISE
WILL LOWER OPERATING LEVEL
UNUSED
PRESS FOR FUNCTION CHECK
Figure 2-4 Circuit Board (Sensing Element Circuits View)
The TIME DELAY adjustment is located on the
sensing element/circuit board side of the housing. It is used to
help stop an oscillating relay output due to agitation or waves
in the vessel. The time delay adjustment can be field-adjusted
from 0 to 60 seconds. The unit is shipped with the TIME DELAY
setting at zero (0) seconds.
The Time Delay adjustment is a 270-Degree turn pot and is at
zero seconds when in the full counter-clockwise position. Do
not force the pot past the stop or damage will occur.
(25 Turn)
TO LOWER DIFFERENTIAL
TIME DELAY
0-60 SECONDS
0
REV
TD
FWD
POST
REV
TD
FWD
9
Installation
DIFFERENTIAL
CLOCKWISE TO RAISE
DIFFERENTIAL
(25 Turn)
COUNTERCLOCKWISE
TP1
60