Ametek IntelliPoint RF RMT Series Installation And Operating Instructions Manual

Two-wire point level switch with manual calibration/set point

Advertisement

Quick Links

IntelliPoint RF™ RMT Series
Two-Wire Point Level Switch
with Manual Calibration/Set Point
International:
Fax:
E-mail:
drexelbrook.sales@ametek.com
Website:
Operating Instructions
+1 215-674-1234
+1 215-674-2731
www.drexelbrook.com
Level Measurement
Installation and
Leader in

Advertisement

Table of Contents
loading

Summary of Contents for Ametek IntelliPoint RF RMT Series

  • Page 1 Leader in Level Measurement Installation and Operating Instructions IntelliPoint RF™ RMT Series Two-Wire Point Level Switch with Manual Calibration/Set Point International: +1 215-674-1234 Fax: +1 215-674-2731 E-mail: drexelbrook.sales@ametek.com Website: www.drexelbrook.com...
  • Page 2 AMETEK Drexelbrook makes no warranty of any kind with regard to the material contained in this manual, including, but not limited to, implied warranties or fitness for a particular purpose. Drexelbrook shall not be liable for errors contained herein or for incidental or consequential damages in connection with the performance or use of material.
  • Page 3 RMTXX1-LM Issue #13 IntelliPoint RF™ RMT Series Two-Wire Point Level Switch with Manual Calibration/Set Point 205 Keith Valley Road, Horsham, PA 19044 Telephone: +1 215-674-1234 Fax: +1 215-674-2731 An ISO 9001 Certified Company E-mail: drexelbrook.info@ametek.com Website: www.drexelbrook.com...
  • Page 4 Contents...
  • Page 5: Table Of Contents

    Contents Section 1: Introduction System Description ..................1 Technology ....................1 Model Number .....................2 Sensing Element List ...................3 Dual Compartment Housing ................4 Section 2: Installation Unpacking ....................5 Mounting and Installation Guidelines ............5 Installation of Flush-Mounted Sensing Elements .........7 Input Wiring ....................8 Spark Protection ..................8 Circuit Board ....................9 Output and LED Status ................11 Sensing Element Connection ...............12...
  • Page 6 Section 1...
  • Page 7: Introduction System Description

    Introduction Section 1: Introduction System Description The AMETEK Drexelbrook, IntelliPoint RMT and RGT Series point level switches detect the presence or absence of material and provide a current output for control functions. The RMT and RGT IntelliPoint™ switches are calibrated through a simple potentiometer adjustment.
  • Page 8: Model Number

    RMTXX1 Series - IntelliPoint RF™ Instruction Manual Model Number IntelliPoint RF Technology RF Admittance Measurement Type Manual Calibration (Standard Sensitivity) Manual Calibration (High Sensitivity) Input Two-Wire Power Supply, 13-30 Vdc Housing No Approvals, NEMA 4X/IP66, M20 X 1.5 conduit entries No Approvals, NEMA 4X/IP66, ¾”...
  • Page 9: Sensing Element List

    Introduction Sensing Element List Application Sensing Element Part Number Pressure/Temperature Wetted Parts 700‐1202‐001 Remote General purpose 13.8 bar @ 232°C (200 PSI @ 450°F)  316/316L SS and PEEK 700‐1202‐021 Integral 700‐1202‐014 Remote  General purpose, longer insertion lengths w/cable attachment and 316/316L SS bottom weight 13.8 bar @ 177°C (200 PSI @ 350°F) 316/316L SS and PEEK 700‐1202‐024 Integral 700‐1202‐018 Remote Proximity 13.8 bar @ 232°C (200 PSI @ 450°F) 316/316L SS and PEEK with 76mm (3) 216SS proximity plate 700‐1202‐028 Integral 700‐1202‐041 Remote  69 bar @ 121°C (1000 PSI @ 250°F) General purpose, high temperature and pressure 316/316L SS and PEEK 700‐1202‐042 Integral 20.7 bar @ 232°C (300 PSI @ 450°F) 700‐1202‐031 Remote  General purpose with FDA approved materials of construction 13.8 bar @ 232°C (200 PSI @ 450°F)  316/316L SS and FDA grade PEEK 700‐1202‐032 Integral 700‐1202‐010 Remote  General purpose for granular materials 13.8 bar @ 232°C (200 PSI @ 450°F)  316/316L SS and PEEK with 7/8 inch dia. 316/316L SS collar 700‐1202‐020 Integral 700‐1202‐033 Remote  316/316L SS and FDA grade PEEK with 7/8 inch dia. 316/316L SS ...
  • Page 10: Dual Compartment Housing

    RMTXX1 Series - IntelliPoint RF™ Instruction Manual Dual Compartment Housing Figure 1-3 Dual Compartment Housing Detail SENSING INPUT/OUTPUT ELEMENT, CUSTOMER CIRCUIT CONNECTION BOARD SIDE SIDE Unlocked Locked Lid Locking Mechanism (CENELEC Systems) Conduit Entries (2) Input/Output Module ¾-inch NPT (FM/FMc Systems) M20 x 1.5 (ATEX/IECEx Systems) LABEL (see below)
  • Page 11: Installation Unpacking

    Installation Section 2: Installation Unpacking Carefully remove the contents of the shipping carton and check each item against the packing list before destroying any packing material. If there is any shortage or damage report it to the factory immediately. Mounting and Installation Guidelines The IntelliPoint RF instrument can be mounted vertically, horizontally, or at an angle.
  • Page 12 RMTXX1 Series - IntelliPoint RF™ Instruction Manual Mounting and Installation Guidelines (continued) The IntelliPoint RF instrument is rated intrinsically safe (I.S.) when power is provided from an I.S. supply. WARNING: The IntelliPoint RF equipment is also rated explosion-proof / flame-proof. When installing in explosion hazardous areas [rated “potentially hazardous”...
  • Page 13: Installation Of Flush-Mounted Sensing Elements

    Installation Mounting and Installation Guidelines (continued) Mount the sensing element as to avoid enhancing electrostatic discharge from the process medium, as is good practice with any thermowell, displacer, or sampler. This includes correct bonding to the tank or silo wall. If installation area is rated explosion-proof and requires conduit seal fittings, they should be used in accordance with company standards and local codes.
  • Page 14: Input Wiring

    RMTXX1 Series - IntelliPoint RF™ Instruction Manual Input Wiring WARNING: If the IntelliPoint instrument is located in a hazardous environment, do not open the enclosure cover or make/break any electrical connections without first disconnecting electrical power at the source. Ensure that the wiring, electrical fittings and conduit connections conform to electrical codes for the specific location and hazard level.
  • Page 15: Circuit Board

    Installation Circuit Board The circuit board is located on the sensing element/circuit side of the housing (marked on label). Remove the housing lid to access the setpoint adjustment status LEDs, time delay adjustment, and configuration jumpers. See Figure 2-4. DIFFERENTIAL SETPOINT CLOCKWISE TO RAISE CLOCKWISE WILL RAISE...
  • Page 16 RMTXX1 Series - IntelliPoint RF™ Instruction Manual 2.6.2 Time Delay Action Time delay action describes whether the relay contacts are delayed from going into the alarm state or recovering from an alarm state. • FWD: Delays system from coming out of alarm. •...
  • Page 17: Output And Led Status

    Tank Condition AutoVerify = disabled Normal Installation Power Normal GREEN Output and LED Status Power High Level Failsafe There are two status LEDs located on the sensing element/ GREEN Tank Empty circuit board side of the housing. The green LED is used to indicate the unit has power.
  • Page 18: Sensing Element Connection

    RMTXX1 Series - IntelliPoint RF™ Instruction Manual Sensing Element Connection Sensing element connects to the rear side of the circuit board and is factory-installed. The sensing element is sealed to the housing and cannot be removed without permanent damage. For IntelliPoint RF instruments that are mounted remotely from the sensing element, an additional housing with terminals is provided to connect the cable from the sensing element.
  • Page 19 Installation Sensing Element Connection (continued) 3 TERMINAL PROBE (TYP) Shield Wire Center Wire (RED) (BLUE) Housing and Bracket are G=Ground Ground Wire S=Shield shown rotated (GREEN) C=Center 90º for clarity. 2 TERMINAL PROBE (TYP) Center Wire (BLUE) Shield Wire (CLIPPED) Ground Wire (GREEN) SHIELD WIRE MUST BE CLIPPED BY USER...
  • Page 20 Section 3...
  • Page 21: Calibration

    Calibration Section 3: Calibration WARNING: Before removing the explosion-proof housing cover in a potentially hazardous area, make certain that the area is safe. When calibration is complete, the cover must be replaced. Setpoint Control There is a single adjustment located on top of the instrument that controls the point at which the Alarm / Normal condition switches.
  • Page 22: Adjustable Differential Controls

    RMTXX1 Series - IntelliPoint RF™ Instruction Manual Adjustable Differential Controls Differential is the hysteresis (dead band), or change in level, DIFFERENTIAL necessary to switch electronic unit from one state to another. It is useful to prevent oscillation "chatter" on those occasions when level happens to be right at switching point or when surface is agitated.
  • Page 23: Calibration Procedures

    Calibration Calibration Procedures All RMT Series controls with bare metal sensing elements are factory-set to switch in all water-based conducting materials. NO calibration adjustment is needed when measuring conductive media. . 3.3.1 Quick Calibration Quick Calibration method is ONLY recommended for horizontally mounted, bare metal, Cote-Shield sensing elements.
  • Page 24 RMTXX1 Series - IntelliPoint RF™ Instruction Manual 3.3.2 Calibration of Horizontal Insulated Sensing Elements or Horizontal Sensing Elements in Insulating Materials 1. Begin with sensing element totally uncovered. 2. Turn the Differential adjustment to the full counter clockwise position. 3. Starting with the SetPoint adjustor in full counter clockwise (ccw) position, slowly turn clockwise (cw) until switch changes state.
  • Page 25 Calibration 3.3.3 Calibration of Vertical Insulated Sensing Elements or Vertical Sensing Elements in Insulating Materials Red LED OFF = normal condition 1. Turn the Differential adjustment to the full counter clockwise position. 2. Set level to where control is desired. [Minimum of 3 inches should cover sensing element.] 3.
  • Page 26 RMTXX1 Series - IntelliPoint RF™ Instruction Manual 3.3.4 Recalibration (Continued) Nonvolatile Memory The IntelliPoint has nonvolatile memory which allows the unit to re-start after power outages without recalibrating. When the IntelliPoint is powered for the first time the internal microprocessor records and stores the “Air” value. This is the uncovered value of the sensor mounted in the vessel.
  • Page 27 Calibration 3.3.6 High Level Fail Safe Blind Calibration of Control w/Flush Sensing Element (Alarm when chute is full at sensor) 1. Start with sensing element uncovered, (no material at sensing element), and tuning SetPoint adjustment to the full counter-clockwise (ccw) position. At this point Red LED will be ON.
  • Page 28 RMTXX1 Series - IntelliPoint RF™ Instruction Manual 3.3.7 Low Level Fail Safe Blind Calibration of Control w/Flush Sensing Element (Alarm when chute is empty at sensor) 1. Start with sensing element uncovered, (no material at sensing element), and tuning the SetPoint adjustor to full counterclockwise (ccw) position.
  • Page 29: Section 4: Spare Parts List

    Spare Parts List Section 4: Spare Parts List Spare Parts List O-ring ........................250-1-75 Housing ¾-Inch NPT Conduit Entry ..............260-2-540 Housing M20 Conduit Entry .................260-2-542 Input/ Output Module ....................385-48-6 Input/ Output Module, Gold Relay ...............385-48-18 Circuit Board RML - Manual Calibration (Std Sensitivity).........385-48-10-MT1 RGL - Manual Calibration (High Sensitivity)........385-48-20-GT1 Integral Sensing Element Cable (PEEK Probes) ..........380-9000-97 Integral Sensing Element Cable (All Other Probes)........380-9000-99...
  • Page 30 Section 5...
  • Page 31: Troubleshooting

    Troubleshooting RF Point Level Troubleshooting Guide Symptom Possible Cause Solution See Section Switch is in alarm and will Sensor is coated by a conductive material and the Need a sensor with a longer Cote-Shield Section 2.2, 5.4 not clear Cote-Shield™ element does not extend far enough element.
  • Page 32: Testing The Electronic Unit

    RMTXX1 Series - IntelliPoint RF™ Instruction Manual Testing The Electronic Unit WARNING: If the IntelliPoint instrument is located in a hazardous environment, do not open enclosure cover or make/break any electrical connections without first disconnecting electrical power at the source. Ensure that wiring, electrical fittings, and conduit connections conform to electrical codes for the specific location and hazard level.
  • Page 33: Testing The Relay Circuits

    Troubleshooting Testing The Electronic Unit (Continued) 10. Turn calibration adjustment counter-clockwise until the Red LED changes again. If more than 1/3 turn is required then the unit is faulty. 11. If the IntelliPoint fails all of the above tests, in most cases the instrument is faulty.
  • Page 34: Testing The Sensing Element

    RMTXX1 Series - IntelliPoint RF™ Instruction Manual Testing The Sensing Element Integral electronics, See figure 2-6 Remove Sensing Element Circuit Board and disconnect cable from circuit board Remote electronics, See figure 2-7 Disconnect remote cable at the sensing element. 1. With the sensing element in the vessel, verify level is below the sensing element 2.
  • Page 35 RMTXX1 Series - IntelliPoint RF™ Instruction Manual Testing The Sensing Element (Continued) A digital ohmmeter will often produce a resistance measurement that is higher than the actual value. Relay and LED Output Status Relay #2 = Alarm Relay #2 = Fault Tank Condition AutoVerify = disabled AutoVerify = disabled...
  • Page 36 RMTXX1 Series - IntelliPoint RF™ Instruction Manual Testing The Sensing Element (Continued) ANALOG ANALOG OHMMETER OHMMETER CENTER OUTER CONDUCTOR CONDUCTOR GROUNDED GROUNDED Red Lug HOUSING HOUSING PACKING PACKING GLAND GLAND DO NOT DISTURB DO NOT DISTURB PROBE MEASUREMENT SHIELD MEASUREMENT Figure 5-4 Checking the Sensing Element Center = Probe...
  • Page 37: Testing The Integral Cable

    RMTXX1 Series - IntelliPoint RF™ Instruction Manual Testing the Integral Cable 1. Disconnect integral cable from electronic. 2. Check for continuity. a. Using an ohmmeter measure the resistances. i. From the center wire connection on the RCA plug to the sensing element active section (center wire) ii.
  • Page 38: Factory Assistance

    Troubleshooting Factory Assistance AMETEK Drexelbrook can answer any questions about your level measurement system. Call Customer Service +1-215- 674-1234 If you require assistance and attempts to locate the problem have failed: • Contact your local Drexelbrook representative • Call the Service department +1-215-674-1234 •...
  • Page 39: 5.10 Equipment Return

    Please include a purchase order even if the repair is under warranty. If repair is covered under warranty, you will not be charged. Ship equipment freight prepaid to: AMETEK-DREXELBROOK. 205 KEITH VALLEY ROAD HORSHAM, PA 19044-1499 COD shipments will not be accepted.
  • Page 40: Specifications

    Specifications Section 6: Specifications RF/Capacitance Technology: None Calibration: High and Low level Modes of Operation: 2mm (0.08 inch) conductive liquids Repeatability: Less than 1 second Response Time: 0 to 60 seconds forward and reverse acting Time Delay: -30 to 70°C (-28 to 158°F) ATEX/IECEx Ambient Electronics: -40 to 70°C (-40 to 158°F) FM/FMc -40 to 85°C (-40 to 185°F)
  • Page 41 RMTXX1 Series - IntelliPoint RF™ Instruction Manual Section 6: Specifications (Continued) Approvals Explosion-proof for use in Class I, Division 1, Groups A, B, C, and D, Dust-Ignition proof for use in Class II and III, Division 1, Groups E, F, and G;...
  • Page 42 Section 7...
  • Page 43: Drawings / Certificates Fm Control Drawings

    Control Drawings Section 7: Drawings / Certificates FM Control Drawings...
  • Page 44 RMTXX1 Series - IntelliPoint RF™ Instruction Manual FM Control Drawings (Continued)
  • Page 45 Control Drawings FM Control Drawings (Continued)
  • Page 46 RMTXX1 Series - IntelliPoint RF™ Instruction Manual FM Control Drawings (Continued)
  • Page 47 Control Drawings FM Control Drawings (Continued)
  • Page 48 RMTXX1 Series - IntelliPoint RF™ Instruction Manual FM Control Drawings (Continued)
  • Page 49 Control Drawings FM Control Drawings (Continued)
  • Page 50 RMTXX1 Series - IntelliPoint RF™ Instruction Manual FM Control Drawings (Continued) COLUMNS 9 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 - 5 6 7 8 - 9 10 11 12 R a T b - 0 0 c d - * * * * a = MEASUREMENT OPTIONS: N = 2 pF AUTO-CAL M = MANUAL-CAL (STANDARD SENSITIVITY)
  • Page 51 Control Drawings FM Control Drawings (Continued) COLUMNS 9 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 - 5 6 7 8 - 9 10 11 12 R a T b - c 0 d e - * * * * a = MEASUREMENT OPTIONS: N = 2 pF AUTO-CAL M = MANUAL-CAL (STANDARD SENSITIVITY)
  • Page 52 RMTXX1 Series - IntelliPoint RF™ Instruction Manual FM Control Drawings (Continued) COLUMNS 9 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 - 5 6 7 8 - 9 10 11 12 R a T b - c 0 d e - * * * * SENSING ELEMENTS: CONTINUED…...
  • Page 53 Control Drawings FM Control Drawings (Continued) MODEL NUMBERS OF APPROVED REMOTE SENSING ELEMENTS 700-mnop-qrs-t LEVEL PROBE m = FAMILY NUMBER: 0 THROUGH 9, BLANK n = FAMILY NUMBER: 0 THROUGH 9, BLANK o = 0 THROUGH 9, BLANK p = 0 THROUGH 9 q = FAMILY NUMBER: 0 THROUGH 9, BLANK r = FAMILY NUMBER: 0 THROUGH 9, BLANK s = FAMILY NUMBER: 0 THROUGH 9...
  • Page 54 RMTXX1 Series - IntelliPoint RF™ Instruction Manual FM Control Drawings (Continued)
  • Page 55 Control Drawings FM Control Drawings (Continued)
  • Page 56 RMTXX1 Series - IntelliPoint RF™ Instruction Manual FM Control Drawings (Continued) COLUMNS 11 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 5 6 - 7 8 9 10 - 11 12 13 14 S a R b T c - 0 0 d e - * * * * a = 2 SIL LEVEL 2 b = MEASUREMENT OPTIONS:...
  • Page 57 Control Drawings FM Control Drawings (Continued) COLUMNS 11 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 5 6 - 7 8 9 10 - 11 12 13 14 S a R b T c - d 0 e f - * * * * a = 2 SIL LEVEL 2 b = MEASUREMENT OPTIONS:...
  • Page 58 RMTXX1 Series - IntelliPoint RF™ Instruction Manual FM Control Drawings (Continued) SPECIFIC CONDITIONS OF USE “The equipment shall not be applied in an explosive dust atmosphere where high electrostatic charging processes are present that could result in propagating brush discharges. See IEC TS60079-32-1 for additional guidance.”...
  • Page 59: Atex Control Drawings

    Control Drawings ATEX Control Drawings...
  • Page 60 RMTXX1 Series - IntelliPoint RF™ Instruction Manual ATEX Control Drawings (Continued)
  • Page 61 Control Drawings ATEX Control Drawings (Continued) COLUMNS 9 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 - 5 6 7 8 - 9 10 11 12 R a T 2 - 0 0 b c - * * * * a = MEASUREMENT OPTIONS: N = 2 pF AUTO-CAL M = MANUAL-CAL (STANDARD SENSITIVITY)
  • Page 62 RMTXX1 Series - IntelliPoint RF™ Instruction Manual ATEX Control Drawings (Continued) COLUMNS 9 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 - 5 6 7 8 - 9 10 11 12 R a T 2 - b 0 c d - * * * * a = MEASUREMENT OPTIONS: N = 2 pF AUTO-CAL M = MANUAL-CAL (STANDARD SENSITIVITY)
  • Page 63 Control Drawings ATEX Control Drawings (Continued) COLUMNS 9 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 - 5 6 7 8 - 9 10 11 12 R a T 2 - b 0 c d - * * * * SENSING ELEMENTS: CONTINUED…...
  • Page 64 RMTXX1 Series - IntelliPoint RF™ Instruction Manual ATEX Control Drawings MODEL NUMBERS OF APPROVED INTRINSICALLY SAFE SENSING ELEMENTS 700-mnop-qrs-t LEVEL PROBE m = FAMILY NUMBER: 0 THROUGH 9, BLANK n = FAMILY NUMBER: 0 THROUGH 9, BLANK o = 0 THROUGH 9, BLANK p = 0 THROUGH 9 q = FAMILY NUMBER: 0 THROUGH 9, BLANK r = FAMILY NUMBER: 0 THROUGH 9, BLANK...
  • Page 65 Control Drawings ATEX Control Drawings (Continued) COLUMNS 11 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 5 6 - 7 8 9 10 - 11 12 13 14 S a R b T 2 - 0 0 c d - * * * * a = 2 SIL LEVEL 2 b = MEASUREMENT OPTIONS: N = 2 pF AUTO-CAL...
  • Page 66 RMTXX1 Series - IntelliPoint RF™ Instruction Manual ATEX Control Drawings (Continued) COLUMNS 11 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 5 6 - 7 8 9 10 - 11 12 13 14 S a R b T 2 - c 0 d e - * * * * a = 2 SIL LEVEL 2 b = MEASUREMENT OPTIONS:...
  • Page 67 Control Drawings ATEX Control Drawings (Continued) SPECIFIC CONDITIONS OF USE 1. The enclosure contains aluminum and is considered a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction. 2.
  • Page 68: Ce Declaration Of Conformity

    1-15-108 1-30-15 4-16-102 4-20-16 Declaration of Conformity AMETEK DREXELBROOK 205 KEITH VALLEY ROAD HORSHAM, PENNSYLVANIA USA, 19044 We declare under our sole responsibility that the product 2 – Wire IntelliPoint Point Level Measurement Systems Model Number RXTX2 / SXRXT2 Series which this declaration relates is in...
  • Page 69: Atex Control Drawings

    Control Drawings IECEx Control Drawings...
  • Page 70 RMTXX1 Series - IntelliPoint RF™ Instruction Manual IECEx Control Drawings (Continued)
  • Page 71 Control Drawings IECEx Control Drawings (Continued) COLUMNS 9 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 - 5 6 7 8 - 9 10 11 12 R a T b - 0 0 c d - * * * * a = MEASUREMENT OPTIONS: N = 2 pF AUTO-CAL M = MANUAL-CAL (STANDARD SENSITIVITY)
  • Page 72 RMTXX1 Series - IntelliPoint RF™ Instruction Manual IECEx Control Drawings (Continued) COLUMNS 9 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 - 5 6 7 8 - 9 10 11 12 R a T b - c 0 d e - * * * * a = MEASUREMENT OPTIONS: N = 2 pF AUTO-CAL M = MANUAL-CAL (STANDARD SENSITIVITY)
  • Page 73 Control Drawings IECEx Control Drawings (Continued) COLUMNS 9 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 - 5 6 7 8 - 9 10 11 12 R a T b - c 0 d e - * * * * SENSING ELEMENTS: CONTINUED…...
  • Page 74 RMTXX1 Series - IntelliPoint RF™ Instruction Manual IECEx Control Drawings (Continued) MODEL NUMBERS OF APPROVED INTRINSICALLY SAFE SENSING ELEMENTS 700-mnop-qrs-t LEVEL PROBE m = FAMILY NUMBER: 0 THROUGH 9, BLANK n = FAMILY NUMBER: 0 THROUGH 9, BLANK o = 0 THROUGH 9, BLANK p = 0 THROUGH 9 q = FAMILY NUMBER: 0 THROUGH 9, BLANK r = FAMILY NUMBER: 0 THROUGH 9, BLANK...
  • Page 75 Control Drawings IECEx Control Drawings (Continued) COLUMNS 11 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 5 6 - 7 8 9 10 - 11 12 13 14 S a R b T c - 0 0 d e - * * * * a = 2 SIL LEVEL 2 b = MEASUREMENT OPTIONS: N = 2 pF AUTO-CAL...
  • Page 76 RMTXX1 Series - IntelliPoint RF™ Instruction Manual IECEx Control Drawings (Continued) COLUMNS 11 AND UP, DO NOT AFFECT SAFETY 1 2 3 4 5 6 - 7 8 9 10 - 11 12 13 14 S a R b T c - d 0 e f - * * * * a = 2 SIL LEVEL 2...
  • Page 77 Control Drawings IECEx Control Drawings (Continued) SPECIFIC CONDITIONS OF USE: 1 THE EQUIPMENT SHALL NOT BE APPLIED IN AN EXPLOSIVE DUST ATMOSPHERE WHERE HIGH ELECTROSTATIC CHARGING PROCESSES ARE PRESENT THAT COULD RESULT IN PROPAGATING BRUSH DISCHARGES. 2 CONSULT THE MANUFACTURER IF DIMENSIONAL INFORMATION ON THE FLAMEPROOF JOINTS IS NECESSARY. 3 AMBIENT TEMPERATURE RANGE: -30°C TO +58°C FOR RXLX/SXRXTX INTELLIPOINT RF LEVEL SYSTEM -30°C TO +70°C FOR RXTX/SXRXTX INTELLIPOINT RF TWO-WIRE POINT LEVEL SYSTEM...
  • Page 78: Mounting And Wiring For Spark Protector Drawings

    RMTXX1 Series - IntelliPoint RF™ Instruction Manual Mounting and Wiring for Spark Protector Drawings...
  • Page 79 Control Drawings Mounting and Wiring for Spark Protector (Continued)
  • Page 80 RMTXX1 Series - IntelliPoint RF™ Instruction Manual Mounting and Wiring for Spark Protector (Continued)
  • Page 81: Adding A Padded Capacitor

    RMTXX1 Series - IntelliPoint RF™ Instruction Manual Adding a Padded Capacitor...
  • Page 82 Control Drawings Adding a Padded Capacitor (Continued)
  • Page 83 RMTXX1 Series - IntelliPoint RF™ Instruction Manual Adding a Padded Capacitor (Continued)
  • Page 84: Dual Seal Assembly For 700 Series Sensing Elements

    Control Drawings Dual Seal Assembly for 700 Series Sensing Elements...
  • Page 85 RMTXX1 Series - IntelliPoint RF™ Instruction Manual Dual Seal Assembly (Continued)
  • Page 86 Control Drawings Dual Seal Assembly (Continued)
  • Page 87 Appendix A...
  • Page 88: Shortening Or Lengthening The Sensing Element

    Appendix Appendix A: Shortening or Lengthening the Sensing Element CAUTION: The insulation length of either Flush Sensing Elements or Insulated Sensing Elements can NOT be changed. Cable Sensing Elements can only be shortened. Instructions are included with each unit. The Need Sometimes your application calls for probe lengths other than the standard 18-inch or longer insertion lengths supplied.
  • Page 89: Ce Installation Supplement

    Sht. APP'D BY 440-0018-731 RMTXX1 Series - IntelliPoint RF™ Instruction Manual ISSUE EDO NO. APP'D DATE 2-16-102 2-1-16 CE Installation Supplement 11-17-100 11-3-17 EMC Installation Supplement Purpose: To provide additional information that is required to be in compliance with the CE mark of conformity and 2014/30/EU Directive. Definitions: 1.
  • Page 90: Ce Installation Supplement (Continued

    RMTXX1 Series - IntelliPoint RF™ Instruction Manual CE Installation Supplement (Continued) Sht. ISSUE 440-0018-731 3. Remote Installations  Sensor port must be connected to the transmitter port by one of the following means: • 401-16 Probe Filter • Coaxial cable run in conduit. •...
  • Page 91 AMETEK, Inc. TERMS AND CONDITIONS OF SALE THE FOLLOWING TERMS/CONDITIONS, TOGETHER WITH ANY OTHER TERMS/CONDITIONS SPECIFICALLY AGREED TO IN WRITING BY SELLER, SHALL APPLY TO ALL ORDERS (“Order(s)”) FROM, AND SALES OF PRODUCTS (“Products”) OR SERVICES (“Services”) TO BUYER. ANY ACCEPTANCE OF ANY ORDER OF BUYER IS CONDITIONED UPON THESE TERMS/CONDITIONS. ANY ADDITIONAL OR DIFFERENT TERMS/CONDITIONS PROPOSED BY BUYER IN ANY DOCUMENT ARE OBJECTED TO AND SHALL NOT BE BINDING UPON SELLER.
  • Page 92 WHETHER ORAL, WRITTEN, EXPRESS, IMPLIED OR STATUTORY. Seller’s prior written consent. Upon completion of Order, Buyer shall NO IMPLIED OR STATUTORY WARRANTIES OF promptly return all Data to Seller together with all copies or reprints thereof then in Buyer's possession or control, and Buyer shall thereafter make no MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE future use, either directly or indirectly, of any Data or any information SHALL APPLY.
  • Page 93 205 Keith Valley Road, Horsham, PA 19044 An ISO 9001 Certified Company Telephone: +1 215-674-1234 Fax: +1 215-674-2731 RMTXX1-LM Issue 13 E-mail: drexelbrook.info@ametek.com EDO# 07-18-117 Website: www.drexelbrook.com...