RMTXX1 Series - IntelliPoint RF™ Instruction Manual

CE Installation Supplement

A.
Purpose:
B.
Definitions: 1.
C.
Installation Specifics:
1. I/O Sensor/Measurement/Control Ports
2. I/O AC Power Port
EMC Installation Supplement
To provide additional information that is required to be in compliance with
the CE mark of conformity and 2014/30/EU Directive.
I/O Sensor/Measurement/Control Port -- Any port which provides
level measurement, control, and/or DC power.
2.
I/O AC Power -- Any port which provides AC main power to the
instrument.
3.
Housing -- Any enclosure where the sensor and transmitter can be
located.
4.
Non-metallic applications -- any application where the sensor is
not surrounded by a metallic surface.
 Wiring must be twisted pair and run in conduit or an equivalent
shielded environment (i.e. shielded braid, cable, etc.).
 The shield terminations must be grounded at the source and
destination ports.
 Wiring must be run separate from AC main power and/or any
signal exceeding 75 volts DC or 50 volts AC.
 Wiring must be run either in conduit or an equivalent shielded
environment (i.e. shielded braid, cable, etc.).
 The shield terminations must be grounded at the source and
destination ports.
440-0018-731
ISSUE
EDO NO.
3
2-16-102
4
11-17-100
A-2
Sht.
1
APP'D BY
of
2
SGA
APP'D
DATE
THP
2-1-16
SGA
11-3-17