Leader in Level Measurement Installation and Operating Instructions ThePoint Series Two Wire Point Level Switch Auto-Calibration or Manual Calibration Selectable Telephone: +1 215-674-1234 Fax: +1 215-674-2731 E-mail: drexelbrook.service@ametek.com Website: www.drexelbrook.com...
Page 2
AMETEK Drexelbrook makes no warranty of any kind with regard to the material contained in this manual, including, but not limited to, implied warranties or fitness for a particular purpose. Drexelbrook shall not be liable for errors contained herein or for incidental or consequential damages in connection with the performance or use of material.
Page 3
EDO # 05-19-110 PMT1-LM Issue# 13 ThePoint Series Two Wire Point Level Switch Auto-Calibration or Manual Calibration Selectable...
Contents Section 1: Introduction ......................1 System Description ....................1 Technology ......................1 Model Number ...................... 2 Housing Dimensions ................... 4 Section 2: Installation ......................5 Unpacking ......................5 Mounting and Installation Guidelines ..............5 Input Wiring ......................8 Output and LED Status ..................8 Electronic Unit .....................
Cote-Shield™ circuitry within the Electronics Unit. This patented Cote-Shield™ circuitry is designed into Figure 1-1 ThePoint series and enables the instrument to ignore the Simple Capacitance effect of buildup or material coating on the sensing element. Probe...
The Point™ Series Introduction Model Number Technology RF Admittance Measurement Type Std Auto Cal Hi Sense .5 pF Auto Cal All Calibration modes are built Std 2 pF Fixed Hi Sense .5 pF Fixed into the standard unit. Modes 10 pF Auto Cal Hi Sense Manual can be changed in the field as 10 pF Fixed...
Page 9
low pressure 1.4 bar @ 232°C (20 PSI @ 450°F) Heavy duty, agitated 700-0202-043 remote 69 bar @ 38°C (1000 PSI @ 100°F) 316SS and TFE tanks or material 13.8 bar @ 232°C (200 PSI @ 450°F) with high bulk density (1) The Point™...
ThePoint™ Series Installation Section 2: Installation Unpacking Carefully remove the contents of the shipping carton and check each item against the packing list before destroying any packing material. If there is any shortage or damage, immediately report it to the factory at + 215-674-1234. Mounting and Installation Guidelines WARNING: ThePoint equipment is rated explosion-proof.
Page 12
Installation Mounting and Installation Guidelines (continued) After system is installed and level is below sensing element, apply power. ThePoint series instrument does not require The Point RF any calibration or setpoint adjustments and is ready to detect instrument is rated change in level.
Page 13
ThePoint™ Series Installation Mounting and Installation Guidelines (continued) • If installation area is rated explosion-proof and requires conduit seal fittings, they should be used in accordance with company standards and local codes. • Mounting sensing element inside a pipe is not recommended.
ThePoint™ Series Installation Input Wiring WARNING: If ThePoint instrument is located in a hazardous environment, do not open enclosure cover or make/break any electrical connections without first disconnecting electrical power at the source. Ensure that wiring, electrical fittings, and conduit connections conform to electrical codes for the specific location and hazard level.
ThePoint™ Series Installation Electronic Unit Remove housing lid to access status LEDs, time delay adjustment, and configuration jumpers. See Figure 2-5. OUTPUT Right = 8mA Alarm 16 mA Normal GREEN LED - POWER Left = 8mA Normal RED LED - ALARM 16 mA Alarm TIME DELAY JUMPER RESET/RECAL...
Page 16
ThePoint™ Series Installation 2.5.4 Failsafe Failsafe describes the level condition that causes the transmitter to go into alarm. • High Level FailSafe (HLFS) is the condition when the probe is covered, the unit goes into alarm. • Low Level FailSafe (LLFS) is the condition when the probe is uncovered, the unit goes into alarm.
ThePoint™ Series Installation Spark Protection Applications involving insulating granulars and insulating liquids may produce a static discharge that can damage the electronics. The RF series instrument is supplied with integral heavy-duty spark protection to prevent static discharges from damaging the electronic circuits. Sensing Element Connection (Integral Sensing Elements) Sensing element connects to the rear side of the circuit board and is factory-installed.
Page 18
ThePoint™ Series Installation Sensing Element Connection (Continued) For ThePoint instruments mounted remotely from sensing element, cable connections from sensing element to Electronic Unit are made to terminals beneath the Electronic Unit. See Figure 2-7. 3 TERMINAL PROBE (TYP) COTE-SHIELD EQUIPOTENTIAL (RED) TERMINAL GROUND...
ThePoint™ Series Installation Calibration ThePoint™ level measurement switch features both Auto- Cal and manual calibration. The standard Auto-Calibration mode is applicable to most liquids and slurries point level measurements. If preferred, the manual calibration can be used and is recommended for some application. ThePoint electronic unit has auto and manual calibration modes built into the standard unit and can be accessed through a simple routine (see section 2.8.5).
Page 20
ThePoint™ Series Installation 2.8.1 Selecting the Calibration Mode for your application (Continued) Application Guide (For instructions on how to access alternate modes see 2.8.4) Application Calibration Mode Liquids and Slurries Auto-Cal Mode #2 Granular /Solids with Bulk Density Manual Cal Mode #7 greater than 20#’s per cubic foot Granular/Solids with Bulk Density Manual Cal Mode #8 (high...
ThePoint™ Series Installation 2.8.3 Using ThePoint with Manual Calibration modes #7, and 8 Warning! Before removing the explosion-proof housing cover in a potentially hazardous are, make certain that the area is safe. When calibration is complete, the cover must be replaced. Make sure that ThePoint is set to either mode #7 (standard Sensitivity) or mode #8 (high sensitivity).
Page 22
ThePoint™ Series Installation 2.8.3 Manual Calibration modes #7, and 8 (Continued) Manual Calibration When material level can be moved Make certain that ThePoint is in manual calibration mode #7 or 8 See Section 2.8.5 Configuration Adjustment RED LED Notes Settings Potentiometer Fail Safe = High Level Turn counter clockwise...
Page 23
ThePoint™ Series Installation 2.8.3 Manual Calibration modes #7, and 8 (Continued) Manual Calibration When material level can not be moved Make certain that ThePoint is in manual calibration mode #7 or 8 See Section 2.8.5 Configuration Adjustment RED LED Notes Settings Potentiometer Fail Safe = High Level...
Page 24
ThePoint™ Series Installation 2.8.3 Manual Calibration modes #7, and 8 (Continued) Note 1: Most water based materials can be considered conductive, such as acids, bases, salt solutions, water based slurries, and very wet granular materials. Carbon black and powdered metals conduct even without water.
Page 25
ThePoint™ Series Installation 2.8.4 Accessing the Calibration Modes 1. On the top side of ThePoint, temporarily remove the shunt from the “Time Delay Selection Jumper” (see Fig. 2-8) and place it on pins 1 & 2 of the 3-pin connector. (Pin 1 is closet to the LEDS) The green LED will go out and the red LED will begin to flash.
Page 26
ThePoint™ Series Installation 2.8.4 Accessing the Calibration Modes (Continued) Definition of Modes Mode 2: Fixed Cal 2pF: 2pF differential, set point locked 2pF above starting capacitance Mode 7: Manual calibration standard sensitivity – pots adjusts from 0 to 65pF Mode 8: Manual calibration High sensitivity – pot adjusts from 0 to 27 pF Mode 6: Fixed Cal 0.5pF: 0.5pF differential, set point locked 0.5pF above starting capacitance...
ThePoint™ Series Troubleshooting Section 3: Troubleshooting WARNING: If ThePoint instrument is located in a hazardous environment, do not open enclosure cover or make/break any electrical connections without first disconnecting electrical power at the source. Ensure that wiring, electrical fittings, and conduit connections conform to electrical codes for the specific location and hazard level.
ThePoint™ Series Installation Testing Electronic Unit Use the following steps to test the electronic unit: 1. Be sure environment is safe before removing lid from housing. 2. Observe failsafe jumper on circuit board on top of electronic unit (shown in Figure 2-5). Move jumper from current setting to alternate setting [HLFS to LLFS or vice versa].
ThePoint™ Series Troubleshooting Over Range If the Green LED is flashing, the instrument has detected the uncovered sensing element capacitance exceeds the limits of the transmitter. Consult factory instructions. Under Range If the Red LED is flashing, the instrument has detected the sensing element capacitance is too small.
Shorted wires should read 0 ohms Short out two conductors Factory Assistance AMETEK Drexelbrook can answer any questions about ThePoint series instrument. Call Customer Service at 1- 215-674-1234. If you require assistance and attempts to locate the problem have failed: •...
Drexelbrook engineers and specialists, and provide detailed information on all aspects of level measurement, including theory and practice of instrument operation. For more information write to: AMETEK Drexelbrook, Communications/ Training Group or call 215- 674-1234. 3.10 Equipment Return...
ThePoint™ Series Troubleshooting 3.11 RF Point Level Troubleshooting Guide Symptom Possible Cause Solution See Section Switch is in alarm and will not Sensor is coated by a conductive material and the Need a sensor with a longer Cote-Shield Section 2.2 clear Cote-Shield™...
ThePoint™ Series Specifications Section 4: Specifications RF/ Capacitance Technology: Dependant Upon Mode Calibration: High and Low level Modes of Operation: 2mm (0.08 inch) Repeatability: conductive liquids less than 1 second Response Time: 0 to 60 seconds forward Time Delay: and reverse acting -40 to 70°C (-40 to 158°F) Ambient Electronics: -40 to 85°C (-40 to 185°F)
ThePoint™ Series Approvals Available Section 5: Approvals Available Equipment Ratings Intrinsically Safe for use in Class I, II, and, III, Division 1, Groups A, B, C, D, E, F and G in accordance with Entity requirements and Control Drawing 420-0004-220-CD; Nonincendive for use in Class I, Division 2, Groups A, B, C, and D;...
ThePoint™ Series Control Drawings ATEX Control Drawings...
Page 51
ThePoint™ Series Control Drawings ATEX Control Drawings (Continued)
Page 52
ThePoint™ Series Control Drawings ATEX Control Drawings (Continued) ATEX AND IECEx APPROVED INTEGRAL 9-14-119 ADD IECEx...UPDATE SENSING ELEMENT OPTIONS SEE TITLE BLOCK APP'D DATE ZONE EDO # DESCRIPTION REVISION HISTORY DREXELBROOK 420-0004-221-CD...
Page 53
ThePoint™ Series Control Drawings ATEX Control Drawings (Continued) ATEX AND IECEx APPROVED REMOTE 6-16-111 ADD IECEx...UPDATE SENSING ELEMENT OPTIONS SEE TITLE BLOCK APP'D DATE ZONE EDO # DESCRIPTION REVISION HISTORY DREXELBROOK 420-0004-221-CD...
Page 54
ThePoint™ Series Control Drawings ATEX Control Drawings (Continued) ATEX AND IECEx APPROVED REMOTE 6-16-111 ADD IECEx...UPDATE SENSING ELEMENT OPTIONS SEE TITLE BLOCK APP'D DATE ZONE EDO # DESCRIPTION REVISION HISTORY DREXELBROOK 420-0004-221-CD...
ThePoint™ Series Appendix A Shortening or Lengthening Sensing Element CAUTION: The length of either Flush Sensing Elements or Insulated Sensing Elements can Not be changed. Cable Sensing Elements can only be shortened. Instructions are included with each unit. The Need Sometimes your application calls for probe lengths other than the standard 18-inch or longer insertion lengths supplied.
AMETEK, Inc. TERMS AND CONDITIONS OF SALE THE FOLLOWING TERMS/CONDITIONS, TOGETHER WITH ANY OTHER TERMS/CONDITIONS SPECIFICALLY AGREED TO IN WRITING BY SELLER, SHALL APPLY TO ALL ORDERS (“Order(s)”) FROM, AND SALES OF PRODUCTS (“Products”) OR SERVICES (“Services”) TO BUYER. ANY ACCEPTANCE OF ANY ORDER OF BUYER IS CONDITIONED UPON THESE TERMS/CONDITIONS. ANY ADDITIONAL OR DIFFERENT TERMS/CONDITIONS PROPOSED BY BUYER IN ANY DOCUMENT ARE OBJECTED TO AND SHALL NOT BE BINDING UPON SELLER.
Page 67
WHETHER ORAL, WRITTEN, EXPRESS, IMPLIED OR STATUTORY. Seller’s prior written consent. Upon completion of Order, Buyer shall promptly return all Data to Seller together with all copies or reprints thereof NO IMPLIED OR STATUTORY WARRANTIES OF then in Buyer's possession or control, and Buyer shall thereafter make no MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE future use, either directly or indirectly, of any Data or any information SHALL APPLY.