Replace A Safety I/O Device; Replacement With 'Configure Only When No Safety Signature; Exists' Enabled - Allen-Bradley Compact GuardLogix 5370 User Manual

Hide thumbs Also See for Compact GuardLogix 5370:
Table of Contents

Advertisement

Chapter 7
Add, Configure, Monitor, and Replace CIP Safety I/O Devices

Replace a Safety I/O Device

116
You can use the Logix Designer application to replace a safety I/O device on an
Ethernet network. If you are relying on a portion of the CIP Safety system to
maintain SIL 3 behavior during device replacement and functional testing, the
Configure Always feature cannot be used. Go to
Only When No Safety Signature Exists' Enabled on page
If the entire routable CIP Safety control system is not being relied on to
maintain SIL 3/PLe during the replacement and functional testing of a device,
the Configure Always feature can be used. Go to
Always' Enabled on page
Safety I/O device replacement is configured on the Safety tab of the Compact
GuardLogix controller.
Figure 21 - Safety I/O Device Replacement

Replacement with 'Configure Only When No Safety Signature

Exists' Enabled

When a safety I/O device is replaced, the configuration is downloaded from
the safety controller if the DeviceID of the new device matches the original.
The DeviceID is a combination of the node/IP address and the Safety
Network Number (SNN) and is updated whenever the SNN is set.
If the project is configured as 'Configure Only When No Safety Signature
Exists' , follow the appropriate steps in
based on your scenario. Once you have completed the steps correctly, the
DeviceID matches the original, enabling the safety controller to download the
proper device configuration, and re-establish the safety connection.
Rockwell Automation Publication 1769-UM022C-EN-P - June 2018
Replacement with 'Configure
Replacement with 'Configure
120.
Table 18
to replace a safety I/O device
116.