If the software indicates
Download to the controller.
Unable to download to the controller. Mismatch between the offline project
and the controller serial number. Selected controller may be the wrong
controller.
Unable to download to the controller. The major revision of the offline
project and the controller' s firmware are not compatible.
Unable to download to controller. The internal safety partner hardware has
failed.
Unable to download to the controller. The firmware update of the controller
is incomplete.
Unable to download to controller. Safety partnership has not been
established.
Unable to download to controller. Incompatible safety task signature
cannot be deleted while the project is safety-locked.
Cannot download in a manner that preserves the safety task signature.
Controller's firmware minor revision is not compatible with safety task
signature in offline project.
Unable to download to controller. Controller is locked. Controller and offline
project safety task signatures do not match.
A nonrecoverable safety fault will occur in the safety controller. No
designated coordinated system time (CST) master exists.
(1) The controller must be safety-unlocked.
5. Follow the directions in this table to complete the download based on
the software's response.
Then
Choose Download. The project downloads to the controller and the Logix Designer application goes
online.
Connect to the correct controller or verify that this is the correct controller. If it is the correct
controller, select the Update project serial number checkbox to allow the download to proceed. The
project serial number is modified to match the controller serial number.
Choose Update Firmware
by clicking Yes.
Replace the controller.
Choose Update Firmware
by clicking Yes.
Cancel this download process and attempt a new download.
Cancel the download. To download the project, you must safety-unlock the offline project, delete
the safety task signature, and download the project.
IMPORTANT: The safety system requires revalidation.
• If the firmware minor revision is incompatible, to preserve the safety task signature, update the
firmware revision in the controller to exactly match the offline project. Then download the offline
project.
• To proceed with the download despite the safety task signature incompatibility, click Download.
The safety task signature is deleted.
IMPORTANT: The safety system requires revalidation.
Choose Unlock. The Safety Unlock for Download dialog box appears. If the Delete Signature
checkbox is selected and you choose Unlock, you must confirm the deletion by selecting Yes.
Check Enable Time Synchronization and click Download to proceed.
Following a successful download, the safety-locked status and safety task
signature of the controller match the project that was downloaded. Safety data is
initialized to the values that existed when the safety task signature was created.
Rockwell Automation Publication 1769-UM022C-EN-P - June 2018
Go Online with the Controller
(1)
. Choose the required revision and click Update. Confirm your selection
(1)
. Choose the required revision and click Update. Confirm your selection
Chapter 11
173