7. Click
to the right of the safety network number to open the Safety
Network Number dialog box.
8. Click Set.
9. Verify that the Network Status (NS) status indicator is alternating red/
green on the correct device before clicking Yes on the confirmation
dialog box to set the SNN and accept the replacement device.
10. Follow your company-prescribed procedures to functionally test the
replaced I/O device and system and to authorize the system for use.
Rockwell Automation Publication 1769-UM022C-EN-P - June 2018
Add, Configure, Monitor, and Replace CIP Safety I/O Devices
Chapter 7