Adjusting Wireless Adapter And Wireless Sensor Settings; To Edit The Wireless Adapter's Settings - Carrier WIRELESS STANDARD SENSOR Installation Manual

Wireless sensors
Table of Contents

Advertisement

Adjusting Wireless Adapter and wireless sensor settings

Adjusting Wireless Adapter and wireless sensor settings
The Wireless Adapter and wireless sensors have preconfigured settings in SensorBuilder that you may need to
adjust for your installation.

To edit the Wireless Adapter's settings

1
In the Driver pane, right-click WS Adapter, and then select Discover Devices.
2
In the Devices pane, select the Wireless Adapter.
3
Click Yes to read its configuration.
4
On the Device configuration > Settings tab, edit the information as needed. See table below.
5
After you have made edits on the Settings tab, right-click the Wireless Adapter in the Devices pane, and then
select Send Configuration.
Field
°F or °C
Reset
Key 1, 2, 3
To edit Wireless Adapter settings for sensors
PREREQUISITE You must have already paired sensors to the Wireless Adapter.
The Wireless Adapter holds the information described below for each sensor. To edit these settings, right-click a
sensor on the Wireless Adapter's Device configuration > Sensors tab, and then select an option.
Field
EnOceanID
Rnet ID
Wireless Sensors
Installation Guide
Notes
Select the format that the Wireless Adapter will use when it sends temperatures to the
i-Vu® application. If you change this setting, you must send the configuration (step 5
above) and then click Reboot.
NOTE If you have i-Vu® controllers loaded with metric applications, you must select
°C.
Click to reset the Wireless Adapter to its factory default settings.
To create security for your Wireless Adapter, you can define keys that a user will have
to enter before SensorBuilder will read the Wireless Adapter's configuration.
The default number for each key is 000. To create new keys, highlight the 3 dots in
each key field, and replace with a number between 000 and 255.
Notes
Every device is given a unique ID number by the manufacturer. (Not editable)
The sensor's address on the Rnet.
40