Specifications - Carrier WIRELESS STANDARD SENSOR Installation Manual

Wireless sensors
Table of Contents

Advertisement

Specifications

Power requirements
Power supply
Protocol
Radio frequency
Transmission range
Protection
Operating environment
Housing
Weight
Dimensions
Compliance
Wireless Sensors
Installation Guide
24 Vac or 24 Vdc ±10% @ 125 mA
24 Vac or 24 Vdc external power supply, Class 2
Customized version of EnOcean
902 MHz (North America) or
868 MHz (Europe and China)
Typically, 60 ft. (18.29 m) maximum from Wireless Adapter, assuming sensor
and Wireless Adapter are separated by no more than 1 drop ceiling or 2 walls
(drywall with metal studs).
Communication Port is optically isolated.
Indoor rated only
0° to 130°F (-17.8° to 54.4°C)
10% to 90% relative humidity (non-condensing)
UL94-5VA plenum rated enclosure, rugged GE C2950 Cycoloy plastic,
black color
4.3 oz. (121.9 g)
4.66 in. x 3.36 in. 1.39 in.
(11.84 cm x 8.53 cm x 3.53 cm)
United States of America:
FCC CFR47, Chapter 1, Subchapter A, Part 15, Subpart B, Class B
Contains FCC ID: SZV-STM300U
Canada:
Industry Canada Compliant, ICES-003, Class B
cUL Listed UL 916,PAZX&, Energy Management Equipment
Europe:
Mark
EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in
residential, commercial and light industry environment
EN50491-3:2009, Part 3: Electrical safety requirements for Home and
Building Electronic Systems (HBES) and Building Automation and Control
Systems (BACS)
Low Voltage Directive: 2014/35/EU
RoHS Compliant: 2011/65/EU
Australia and New Zealand:
C-Tick Mark, AS/NZS 61000-6-3