Installing The Wireless Adapter And Sensors; To Install The Wireless Adapter - Carrier WIRELESS STANDARD SENSOR Installation Manual

Wireless sensors
Table of Contents

Advertisement

Installing the Wireless Adapter and sensors

Installing the Wireless Adapter and sensors
CAUTION To provide accurate values, a wireless sensor should be in its permanent location for at least 15
minutes before you calibrate it.
To install the Wireless Adapter (page 30)
To install a Standard or Plus sensor (page 32)
To install a Pro-F sensor (page 34)
To install a Motion/Lux sensor (page 35)
To install a Window/Door sensor (page 36)
Troubleshooting the wireless sensor installation (page 39)

To install the Wireless Adapter

Rnet wiring specifications
NOTE Use the specified type of wire and cable for maximum signal integrity.
Description
Conductor
Maximum length
Insulation
Color Code
Shielding
UL temperature rating
Voltage
Listing
WARNING Do not apply line voltage (mains voltage) to the Wireless Adapter.
Wireless Sensors
Installation Guide
4 conductor, shielded or unshielded, CMP, plenum rated cable
22 AWG (7x0096) bare copper
500 feet (152 meters)
Low-smoke PVC (or equivalent)
Black, white, green, red
If shielded, Aluminum/Mylar shield (100% coverage) with TC drain wire
32–167°F (0–75°C)
300 Vac, power limited
UL: NEC CL2P, or better
30
CARRIER CORPORATION ©2018
All rights reserved