To preserve battery life:
Maintain at least 700 lux in the space where the sensor is installed, and set the sensor's Heartbeat interval
and COV threshold to the default numbers or higher. Low lux and frequent signals can significantly impact
battery life.
The sensor is turned off when it ships from the factory. To turn it on, press the Learn button for 5 seconds. If
you find that you will not be using the sensor immediately, you can turn if off again by pressing the Learn
button for 10 seconds. See step 5 in Pair sensors to the Wireless Adapter (page 23) for the location of the
Learn button.

To install a Motion/Lux sensor

1
To remove the mounting plate from the sensor, twist the mounting plate counter-clockwise until it stops, then
remove it.
2
Insert the 1/2 AA 3.6V 1200 mA battery into the battery socket.
3
Attach the mounting plate to ceiling or wall using the provided mounting screws.
Tab
Wireless Sensors
Installation Guide
Tab
35