Carrier AQUAZONE 50RHC Operating And Troubleshooting
Carrier AQUAZONE 50RHC Operating And Troubleshooting

Carrier AQUAZONE 50RHC Operating And Troubleshooting

Solid-state heat pump controls
Hide thumbs Also See for AQUAZONE 50RHC:

Advertisement

Quick Links

AQUAZONE
TM
50RHC,RVC,RHR,RVR
RDS,RHS,RVS,HQL,VQL,KQL,RTG,RWS
Complete
C
Deluxe D
Solid-State
Heat Pump Controls
Control Operation and Troubleshooting
Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ............................
1
GENERAL ............................................
12
INSTALLATION .......................................
2-9
Wiring Requirements ...................................
2
Wiring Connections ....................................
2
Jumper Settings ........................................
2
Complete C Control .....................................
8
WATERCOIL FREEZE PROTECTION
(FP1)
LIMIT
SETTING
AIR COIL FREEZE PROTECTION
(FP2)
LIMIT SETTING
Deluxe O Control .......................................
8
WATERCOIL FREEZE PROTECTION
(FP1)
LIMIT
SETTING
AIR COIL FREEZE PROTECTION
(FP2)
LIMIT SETTING
ALARM RELAY SETTING
....................................
9,10
......................
9
2
Deluxe D Control DIP Switches .........................
9
D]PSWITCH
BANK
1 (S l)
($2)
.... 10
.............................
11-16
Complete C Control Indicators.........................
lI
11
STANDBY MODE
LOCKOUT MODE
EMERGENCY HEAT MODE
HIGH-PRESSURE SWITCH
(HP)
LOW-PRESSURE SWITCH
(LP)
WATERCOIL FREEZE PROTECTION
(FP1)
AIR COIL FREEZE PROTECTION
(FP2)
CONDENSATE OVERFLOW
(CO)
OVER/UNDER VOLTAGESHUTDOWN
PERFORMANCE MONITOR
(PM)
ANTI-SHORT CYCLE PROTECTION
RANDOM START
SWAPPED FP1/FP2 THERMISTORS
SENSORS
Page
......................................
13
EXTENDED COMPRESSOR OPERATION MONITOR
STANDBY/FAN ONLY MODE
HEATING STAGE 1 MODE
HEATING STAGE 2 MODE
HEATING STAGE 3 MODE
EMERGENCY HEAT MODE
NIGHT LOW LIMIT (NLL) STAGED HEATING
Thermostat Inputs ....................................
14
DELUXE D CONTROL
TROLIBLESHOOTING
...............................
16-20
Field Inputs ...........................................
16
Sensor Inputs .........................................
16
Sensor Outputs .......................................
17
Test Mode .............................................
17
l MPORTANT: Read the entire instruction manual before
/
starting inst_dlation.
]
SAFETY
CONSIDERATIONS
Read and follow mmmfacturer instructions cguefully. Fol-
low all local electrical codes during installation. All wiring
must conform to local and national electrical codes, hnproper
wiring or installation may dalnage sensol:
Undel,stand the signal words DANGER, WARNING and
CAUTION. These words gueused with the safety alert symbol.
DANGER identifies the most serious hazards which will result
in severe pel,sonal inju U or death. WARNING signifies a haz-
_ud which could result in personal inju U or death. CAUTION
is used to identify unsafe practices which would result in minor
personal inju U or property damage.
GENERAL
Aquazone Complete C and Deluxe D electronic heat pump
controls are durable, microprocesso>based controllers used to
improve the safety mid operation of Aquazone water source
heat pumps. The microprocessor board is specifically designed
to protect against building electrical system noise contamina-
tion mid radio fiequency interference.
The Complete C control base model is a low cost, easy to
use control that provides all the necessa U features for water
source heat pump safety mid operation. The Complete C
control features a light-emitting diode (LED) to indicate high
pressure, low pressure, low voltage, high voltage, air/water
freeze protection, condensate overflow and control status. The
Complete C control is compatible with most heat pump
thermostats, but is not compatible with Heat/Cool thermostats.
Manufacturer
reserves the right to discontinue, or change at any time, specifications
or designs without notice and without incurring obligations.
PC 111
Catalog No. 535-00058
Printed in U.S.A.
Form 50H,K,R-2T
Pg 1
6-05
Replaces:
50H,K,R-1T

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AQUAZONE 50RHC and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Carrier AQUAZONE 50RHC

  • Page 1: Table Of Contents

    AQUAZONE 50RHC,RVC,RHR,RVR RDS,RHS,RVS,HQL,VQL,KQL,RTG,RWS Complete Deluxe D Solid-State Heat Pump Controls Control Operation and Troubleshooting Instructions CONTENTS Page Deluxe D Control ........Page • LED INDICATORS SAFETY CONSIDERATIONS ......EXTENDED COMPRESSOR OPERATION MONITOR GENERAL ..........STANDBY/FAN ONLY MODE HEATING STAGE 1 MODE INSTALLATION ........
  • Page 2: Installation

    The Deluxe D control is an advanced microprocessor-based Wiring Requirements control designed maximum application flexibility. 1. All wiring must be in compliance with all applicable local includes all of the Complete C control features plus 3 LED and national codes. status indicators and several addfliomd features for extensive...
  • Page 3 START ASSIST (WHEN NEEDED) COMPONENT LOCATION T3 T2 GROUND L5 L2 LI --BLU i- oo CAP E TRANS N0_ USE_ G/YF_- NOTE ,..,a NOTES: LEGEND 1. Compressor and blower motor thermally protected internally. -- Alarm Relay Contacts Field Wiring Terminal Block 2.
  • Page 4 LOCATION COMPONENT BRN* RED* -+,g NOTE S?ARTASS+S_ (WH_ _EEBED) NEUTRAJ+ ON Z6_V SYSTEMS rED+ BLU+ CO_PRCSS_ SEE NOTE "+_ ..¢B+ TRA_S _--""a- YEL O_ WIll Z _LU _-2q]ISEE mOTE + _YEL (208V) (Z_SV) SEE NOTE IONWORKS NOTES: LEGEND 1. Compressor and blower motor thermally protected internally.
  • Page 5 COMPONENT LOCATION BRN* NOTE 7 NOTE _RVS POWER SUPPLy REFER TO DATA PLATE COPPER CONDUCTORS ONLy NOTE LEGEND NOTES: 1. Compressor and blower motor thermally protected internally. -- Alarm Relay Contacts -- Light-Emitting Diode _,,c'__ 2. All wiring to the unit must comply with NEC and local codes. -- Blower Contactor Loss of Charge Pressure Switch Thermistor...
  • Page 6 NOTE NOT_ TYpiCAL p_M_ T-STAT SEE NOTE COOUNG 2_*VAC COMMON GROUND _:: , SEE NOTE 6 FO_ D_¥ CO_TACT_0_ A_A_M SEE NOIE POWER SUPPLY GENERATOR PUM_ CAP TU_ NOTS 2 AND START ASSIST (WN_N NEED_D_ COMPONENT LOCATION COMPRESSOR ..CArS YEL _ POWER SUPPLY...
  • Page 7 NOT_ 7 --_LU __BRN s_A_ ASS_T __GR SE _ NO_E _BRN ..BRN * COHPONENTLOCATION LEGEND NOTES: 1. Compressor and blower motor thermally protected internally. Alarm Relay Contacts Loss of Charge Pressure Switch 2. All wiring to the unit must comply with NEC and local codes. Blower Contactor Motorized Valve Condensate...
  • Page 8: Complete C Control

    Complete C Control (Fig. 6) WATER COIL FREEZE PROTECTION (FPI) LIMIT SETTING--Select jumper 3 (JW3-FPI Temp) choose FPI limit of either 30 F or 10 E To select 30 F as the limit, DO NOT clip the jumper. To select 10 F as the limit, clip the jumper.
  • Page 9: Configuration

    Com2 Coml Demuxe D 17B0002N01 AL2 Dry [cro Low voltage molex connection for wiring unit harness - Low voltage molex connection electric heat harness Fig. 7 -- Deluxe D Board CONFIGURATION Deluxe D Control DIP Switches -- The Deluxe control has 2 DIP (dual in-line package) switch banks.
  • Page 10: Deluxe D Control Accessory Relay Configurations

    Table 2 -- DIP Switch Block S2 -- O/13 Thermostat Type -- Switch 4 provides selectiou for heat Accessory 2 Relay Options pump O/B thermostats, O is cooliug output. B is heating out- put. Select ON for thermostats with O output. Select OFF for ACCESSORY DIP SWITCH POSITION...
  • Page 11: Control Operation

    CONTROL OPERATION Table 5 -- Complete C Control LED Code and Fault Descriptions Complete C Control Indicators -- The status on the Complete C control displays file current status of the FAULT DESCRIPTION CODE Complete C control. If in Test mode, the LED will flash the No fault in memory There has been no fault since code of the last fault and the almm relay will cycle the stone...
  • Page 12: General

    STANDBY M ODE -- The Y and W termimds me not active than 2 ° F per 30 continuous seconds during a compressor in Standby mode, however the O and G terminals may be cycle to be recognized as a FP2 fault. The FP2 input active, depending on the application.
  • Page 13: Deluxe D Control

    the impurities from the drain pan mid coil dust or dirt create the conductance. A second ground wire with appropriate terminal 90.0 to the drain pan cml be used with file control to replace the air coil ground path. The condensate sensor cml also be any open contact that closes upon a fault comlection.
  • Page 14: Thermostat Inputs

    HEATING STAGE 1 MODE --hi Heating Stage 1 mode, the Thermostat Inputs fan enable and compressor relays are turned on immediately. COMPLETE C CONTROL Once the demand is removed, the relays are turned off and the Y and W Terminals Terminals Y and W have l-second control reverts to Standby...
  • Page 15 Table 8 -- Deluxe D Control System Inputs SYSTEM INPUTS NIGHT SETBACK UNIT OPERATING UNIT OPERATION Emergency Night TYPE Override MODE* IMPACTS Shut Down Setback (NSB) (OVR) (ESD) (NSB) NONE UNIT SHUT DOWN NONE NONE NORMAL OPERATION DIGITAL ALL (EXCEPT INVALID) DIGITAL MECHANICAL STANDBY / OFF...
  • Page 16: Communication Ports

    Table 10 -- Deluxe D Control -- Input Combinations -- DIP Switch Block 2 ($2) UNIT SIGNAL ON SWITCH 2 DIP 7 UNIT OPERATION IMPACT OPERATING MODE* STANDBY / OFF WITH AUTO. DEHUMIDIFICATION STANDBY / OFF ENERGIZED FAN HIGH FAN LOW WITH AUTO. DEHUMIDIFICATION FAN 1 SIGNAL ENERGIZED FAN HIGH...
  • Page 17: Sensor Outputs

    Sensor Outputs Test Mode relay is 24 vac and can Compressor Test mode can be entered for 20 minutes by be verified using a voltmetel: The fan signal is passed through shorting the test pins. For diagnostic ease at the thermostat, the board to the external fan relay.
  • Page 18 Table 11 -- Complete C Control Input/Output Reference CONNECTION INPUT OR OUTPUT DESCRIPTION 24 vac 24 vac (grounded common) Connect to thermostat -- Y output call for compressor Connect to thermostat -- W output call for Heating 2 or Emergency Heat Connect to terminal -- O output call for reversing valve with cooling Connect to thermostat -- G output call for fan Connect to thermostat fault light -- 28 va at 24 vac or dry alarm...
  • Page 19 Table 13 -- Troubleshooting FAULT HEATING COOLING POSSIBLE CAUSE SOLUTION Main Power Problems Green Status LED Off Check line voltage circuit breaker and disconnect. Check for line voltage between L1 and L2 on the centactor. Check for 24 vac between R and C on controller.
  • Page 20 Too high airflow Unit oversized Recheck loads and sizing check sensible cooling load and heat pump capacity. LEGEND RV -- Reversing Valve Copyright 2005 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs...