12.1.5 Mapping Status
If the DeviceNet Network Diagnostic parameter (Pr S.01.006) indicates "Init Failed", a
mapping configuration error has been could have been detected. The reason for the
error is indicated by the SI-DeviceNet input mapping status parameter (Pr S.01.022)
and the SI-DeviceNet output mapping status parameter (Pr S.01.023).
When a mapping error has been corrected, reset the SI-DeviceNet module by setting
PrS.01.002 or MM.007 to On (1).
The mapping error codes are described in Table 12.5.
Table 12.5 Mapping error codes
Value
0
1
2
3
4
5
6
7
8
9
10
12.1.6 Alarms
If the SI-DeviceNet detects an alarm during operation, it will cause the drive to display
the appropriate alarm on the drive keypad. If more than one alarm is present, it will be
shown as "first-in-first-out" (FIFO) order.
Value
0
1
2
3
4
5
6
7
8
9
72
Text
No error
No error has been detected during mapping initialisation
Par impossible
The parameter may not exist or may not be readable
Hole in mapping
Cyclic data mapping parameters are not contiguous
Two or more cyclic data mapping configuration
Dup mapping
parameters have been configured with the same
destination parameter reference
The length of the mapped parameters exceeds the length
Length exceed
of the selected assembly object
Obj not support
The selected assembly object is not supported
Pre &
If the predefined object is selected, the data alignment
uncompress
must be set to 16 bits
The IN and OUT objects both must be predefined objects,
Type unmatched
or neither
Memory fault
Failed to allocate memory for mapping
No mapping
No parameter is assigned to the mapping
Reserved
Reserved
Text
No alarm
No alarm.
User Prog
A user program alarm has been generated.
eCMP
An eCMP alarm has been generated.
FS Usage
A file system alarm has been generated.
Too Hot
Module temperature is too high.
In Mapping
Error with Input mapping setup.
Out Mapping
Error with Output mapping setup.
Fieldbus Initialization failed, possibly due to external 24 V
Fbus Init
missing or baud rate detection failed.
Read Err
Error during reading from a mapped parameter.
Write Err
Error during writing to a mapped parameter.
Description
Description
SI-DeviceNet User Guide
Issue Number: 2